| I.B. 29C892B | |
| Table 4.1 Troubleshooting Guide |
|
|
| |
|
|
|
|
|
|
| Symptom | Probable Cause | Possible Solution(s) | Reference |
|
|
|
|
|
|
|
| “Low Battery – Replace Soon” |
| Replace with Lithium battery or use |
|
|
| displayed as on/off is | Dead Battery | Aux. supply #PRTAAPM, Table 2.2 |
| |
| auxiliary power module |
| |||
| depressed |
|
|
| |
|
|
|
|
| |
|
|
|
|
|
|
| “Connection Failure” when | Custom phone cord not | Check connection to OPTIMizer or |
|
|
| plugged into OPTIMizer or | Paragraphs |
| ||
| selecting “Find Address” | trip unit |
| ||
| OPTIM trip unit |
|
| ||
|
|
|
|
| |
|
|
|
|
|
|
| OPTIMizer powers down | Battery power is insufficient for | Change battery | Paragraph |
|
| repeatedly | proper operation |
| ||
|
|
|
| ||
|
|
|
|
|
|
| Warning displayed while | Short delay slope is not set to | Change short delay slope and long | Paragraph |
|
| flat; long delay time not set to |
| |||
| changing long delay slope | delay time | trip curves Appendix A |
| |
|
| ||||
|
|
|
|
| |
|
|
|
|
|
|
|
| “Save” not pressed before | Press save and then select |
|
|
| Setpoints not saved after | “Select” | simultaneously | Paragraph |
|
| changing |
|
|
| |
| Password not entered first | Enter Password |
|
| |
|
|
|
| ||
|
|
|
|
|
|
| “None” displayed when | Trip unit is a | Replace with energy version if function | I.B. 29C891 |
|
| selecting THD | is needed |
| ||
|
|
|
| ||
|
|
|
|
|
|
| “None” displayed when | Trip unit is a | Replace with energy version if function | I.B. 29C891 |
|
| selecting harmonic content | is needed |
| ||
|
|
|
| ||
|
|
|
|
|
|
| Breaker does not trip | Auxiliary power module not | Plug auxiliary power module into | Paragraph |
|
| during trip test | plugged into OPTIMizer | OPTIMizer |
| |
|
|
| |||
|
|
|
|
|
|
| OPTIMizer does not respond | Incorrect key press | Let OPTIMizer time out for 30 seconds. | Paragraph |
|
| to pressing on/off | Unit will shut off or go to main menu |
| ||
|
|
|
| ||
|
|
|
|
|
|
| OPTIMizer turns off after | Energy saver powered unit off |
|
|
|
| several minutes (no | Use auxiliary power module | Paragraph |
| |
| automatically after 2 1/2 minutes |
| |||
| auxiliary power) |
|
|
| |
|
|
|
|
| |
|
|
|
|
|
|
| “Connection Failure” when | Invalid address entered under | Check trip unit address and | Paragraph |
|
| “Select Address” | under “Select Address” main menu item |
| ||
| selecting menu item while |
|
| ||
|
|
|
|
| |
| connected to INCOM network | Auxiliary power not used | Use auxiliary power module | Paragraph |
|
|
|
| |||
|
|
|
|
|
|
| Ground pickup LED on trip | Current value selected is below | Depress trip unit reset pushbutton | Appropriate trip curves |
|
| unit does not flash when | then increase test current or decrease |
| ||
| ground fault pickup setting | Appendix A |
| ||
| ground test initiated | ground pickup level |
| ||
|
|
|
| ||
|
|
|
|
|
|
| Long nor short Pickup LEDs | Current value selected is below | Depress trip unit reset pushbutton | Appropriate trip curves |
|
| on trip unit do not flash when | then increase test current or |
| ||
| phase pickup setting | Appendix A |
| ||
| phase test initiated | decrease phase pickup level |
| ||
|
|
|
| ||
|
|
|
|
|
|
| Test will not initiate when test | Trip unit was not reset after | Press trip unit reset button | I.B. 29C891 paragraphs |
|
| current is entered and saved | previous test | and |
| |
|
|
| |||
|
|
|
|
|
|
| OPTIMizer does not turn | On/off button was not | Depress on/off button for at least | Paragraph |
|
| on when pressing on/off | depressed | 2 seconds |
| |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
Effective 8/99