Emerson 10-30kVA installation manual UPS Electrical Characteristics, UPS terminal

Models: 10-30kVA

1 80
Download 80 pages 58.87 Kb
Page 45
Image 45

UPS Specifications

6.4UPS Electrical Characteristics

Table 10 UPS terminal

Input (for single-input unit)

 

Nominal

Maximum

 

OCP

 

Maximum Recommended Lug

 

 

 

 

 

Unit

Input

Input

OCP

Device

 

Lug T&B

Lug T&B

Rating

Current

Current

Current

Rating

Bolt Size

One Hole 54000

One Hole REDDY

10

28

35

42

45

6M (1/4”)

54105

62204

 

 

 

 

 

 

 

 

15

42

53

63

70

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

20

56

70

84

90

6M (1/4”)

54107

62204

 

 

 

 

 

 

 

 

30

83

104

125

125

6M (1/4”)

54152

62205

 

 

 

 

 

 

 

 

Rectifier input (for dual input unit only)

 

Nominal

 

Maximum

 

OCP

 

Maximum Recommended Lug

 

 

 

 

 

 

Unit

Input

 

Input

OCP

Device

 

Lug T&B

Lug T&B

Rating

Current

 

Current

Current

Rating

Bolt Size

One Hole 54000

One Hole REDDY

10

25

 

31

37

40

6M (1/4”)

54130

62204

 

 

 

 

 

 

 

 

 

15

37

 

47

57

60

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

 

20

50

 

63

76

80

6M (1/4”)

54107

62204

 

 

 

 

 

 

 

 

 

30

75

 

94

113

125

6M (1/4”)

54152

62205

 

 

 

 

 

 

 

 

Bypass input (for dual input units)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Recommended Lug

 

 

Nominal

 

 

OCP

 

 

 

 

 

 

 

 

Lug T&B

Lug T&B

 

Unit

Input

 

OCP

Device

 

One Hole

One Hole

 

Rating

Current

 

Current

Rating

Bolt Size

54000

REDDY

 

10

28

 

35

35

6M (1/4”)

54105

62204

 

 

 

 

 

 

 

 

 

 

15

42

 

53

60

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

 

 

20

56

 

70

70

6M (1/4”)

54107

62204

 

 

 

 

 

 

 

 

 

 

30

83

 

104

110

6M (1/4”)

54152

62205

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

 

OCP

 

Maximum Recommended Lug

 

 

 

 

 

Unit

Output

OCP

Device

 

Lug T&B

Lug T&B

Rating

Current

Current

Rating

Bolt Size

One Hole 54000

One Hole REDDY

10

 

28

35

35

6M (1/4”)

54130

62204

 

 

 

 

 

 

 

 

15

 

42

53

60

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

20

 

56

70

70

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

30

 

84

105

110

6M (1/4”)

54108

62205

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCP

 

Maximum Recommended Lug

 

 

 

 

 

 

 

 

Unit

Battery

OCP

Device

 

Lug T&B

Lug T&B

Rating

Current

Current

Rating

Bolt Size

One Hole 54000

One Hole REDDY

10/15

 

55

55

70

6M (1/4”)

54106

62204

 

 

 

 

 

 

 

 

20/30

 

110

110

125

8M (5/16”)

54153

62212

 

 

 

 

 

 

 

 

 

39

Page 45
Image 45
Emerson 10-30kVA installation manual UPS Electrical Characteristics, UPS terminal

10-30kVA specifications

The Emerson 10-30 kVA, 208V uninterruptible power supply (UPS) solution is a robust system designed to provide reliable power protection for critical applications in commercial and industrial settings. This UPS is ideal for safeguarding IT equipment, communication systems, and other sensitive electronics against power disturbances and interruptions.

One of the standout features of the Emerson 10-30 kVA UPS is its modular design, allowing for flexibility and scalability. This means that as the power needs of a facility grow, the UPS can be easily expanded without requiring a complete system overhaul. This modularity contributes to a more efficient use of resources and minimizes operational costs.

The UPS also incorporates advanced technologies such as double-conversion online architecture, which provides the highest level of power quality. This technology ensures that the output power is consistently clean and stable, effectively eliminating harmful voltage fluctuations and frequency variations. Consequently, connected load receives a pure sine wave output, preventing potential damage or operational issues with sensitive equipment.

Another key feature is the high efficiency rating of the Emerson UPS, which exceeds 95 percent in typical operating conditions. This high efficiency translates to reduced energy costs and a smaller carbon footprint, aligning with modern sustainability goals. The cooling system is designed to be efficient as well, ensuring optimal performance while maintaining a compact footprint.

The user-friendly interface enhances operability, featuring an intuitive LCD display that allows for easy monitoring of critical power parameters. Users can access real-time data related to battery health, load levels, and operational status, which aids in effective management of the power supply.

Battery management is another critical aspect of the Emerson UPS. It employs advanced battery management technologies to ensure optimal battery life and performance. Features such as intelligent battery testing and monitoring help predict potential battery failures before they occur, allowing for proactive maintenance and minimized downtime.

In summary, the Emerson 10-30 kVA, 208V UPS offers a combination of modularity, high efficiency, advanced technologies, and effective power management features that cater to the demanding needs of critical applications. With its reliable performance and user-friendly operation, this UPS solution is an excellent choice for organizations looking to protect their valuable equipment from power disturbances.