4. TECHNICAL CHARACTERISTICS

4.2. TECHNICAL CHARACTERISTICS

MECHANICAL

Metal 19” rack case, 2 units high

IP51 Protection (as per IEC 529)

Local HMI: LCD (2 rows, 16 characters) and 20 key keyboard

Rear connection for wiring: 4 blocks, 12 terminals each (6 blocks when optional expansion board)

Dimensions: 437 x 164 x 88 mm

Weight: Net 6 kg. Shipping 7 kg.

ELECTRICAL

Frequency:

50 or 60 Hz (selectable by setting)

Rated current:

1 or 5 A (different models)

DC Power Supply

48/125 Vdc or 110/250 Vdc (different models)

Operational range

80% to 120% of rated values

Digital Input Voltage

For standard models: 48-125, 110-250 VDC

 

 

(according to selected model). For special models,

 

 

please refer to section 4.1.1.

Thermal Capacity

Current circuits

 

- Permanent

4 x In

- 3s duration

50 x In

- 1 s duration

100 x In

Temperature ranges

 

-Operation

-20º C to + 55ºC

-Storage

-40ºC to + 70ºC

Humidity

Up to 95% without condensation

Trip contacts:

 

 

AC

 

 

-Continuous Capacity

16A

 

-Rated Breaking Capacity

4000VA

 

-Make

25A for 4 sec

 

-Operating Time

8 ms or less

 

DC Breaking Capacity

 

 

- Resistive

9A at 30V

 

- Resistive

0.65A at 100V

- Inductive(L/R=40 ms)

0.5A at 30V

Burden

0.5 VA at Ir = 5 A

 

-Current circuits

Consumption:

0.1 VA at Ir = 1A

 

 

-At DC rated voltage

12 W idle state

 

 

16 W all relays activated

-Digital inputs

8 mA (1 W at Vrated = 125 VDC)

Accuracy

 

 

-Current

5%

 

-Time

5% or 30ms (whichever is greater)

- Error index

Class E-5 as per IEC 255-4

Repeatability

 

 

-Operating value

1%

 

-Operating time

2% or 30 ms (whichever is greater)

22

DBF Breaker Failure Protection

GEK-106168E

Page 29
Image 29
GE GEK 106168E manual Technical Characteristics, Mechanical, Electrical