2. OPERATION LOGIC
2.2.5 BUILT-IN SELF-CHECKING UNIT
The digital technology of the DBF system allows providing a
Two
In addition, there is a hardware test for the Target LEDs, which lights them all up when the button TARGET RESET is pressed. The
2.3. ANALYSIS FUNCTIONS.
The DBF system includes an event recorder and an oscillography waveform recorder with a resolution of 1 ms for the first one, and 1 sample for the second one (1.04 ms at 60 Hz and 1.25 ms at 50 Hz). To avoid the loss of date/time and oscillography records during any Vdc power failure, the unit is equipped with a capacitor, which allows the information to be kept for at least 24 hours after power loss.
2.3.1 EVENT RECORDER.
The DBF system keeps a record of the last 144 events and stores for each one the following information: date and time (accurate to one millisecond), the type of event, current RMS values during the event, and the state of the unit (set of digital signals that describes the status of the relay at any given moment in time).
This event recorder is stored in a
The list of events that the relay stores are factory fixed, and corresponds to standard relevant situations/operations, like Settings Change, Program initiate, Active Table 1, Opening 52 phase C, Closing 52 phase C, Digital Input 1 Activated, etc.
2.3.1 OSCILLOGRAPHY
The DBF unit stores up to 4 oscillography records, with a resolution of 16 samples per cycle. Each record has a maximum capacity of 66 cycles. The number of
∙Date and time.
∙Name of the signal that triggered the oscillography.
∙Active settings table when recording
∙Digital information (Status of internal digital signals)
∙Instantaneous rms values of currents (IA, IB, IC and IN)
A configurable mask is available for selecting which functions or internal signals are able to trigger the oscillography. It can either be triggered by a configurable digital input, by a command received from the communication program (GE_LOCAL), or directly from the HMI.
10 | DBF Breaker Failure Protection |