![](/images/new-backgrounds/1192173/19217337x1.webp)
2. OPERATION LOGIC
2.4. CONTROL
2.4.1 TABLES OF SETTINGS
The DBF system has two types of settings stored in
∙Generic Settings.
∙Specific Settings.
The Generic settings are grouped as follows:
GENERAL SETTINGS
BREAKER SETTINGS
ACTIVE TABLE SETTINGS
OSCILLOGRAPHY MASK
FUNCTION PERMISSION
For the specific settings, the DBF allows to have up to 3 independent setting tables. These specific settings are grouped as follows:
50BF SETTINGS INTERNAL ARC SETTINGS
Only one setting table is active at a given time, and this is the table used by the system to run the different functions included in it.
There is an "ACTIVE TABLE" setting that determines the settings table that is active at a given moment.
The active settings table can be changed by means of up to 2 digital inputs, referred to as "ACTIVE TABLE SELECT 0" and "ACTIVE TABLE SELECT 1" which allow up to 4 combinations from 0 to 3. To do this it is necessary to configure (using
The selected combination is obtained from the binary coding of the 2 inputs mentioned (see following table). The
Table Selection | Table Selection | Active Table |
|
|
|
0 | 0 | Selected by setting |
0 | 1 | 1 |
1 | 0 | 2 |
1 | 1 | 3 |
NOTE: if the inputs are programmed and used, energizing them, this selection has priority over the "ACTIVE TABLE" setting and the table which is in fact used is determined by the status of the digital inputs.
12 | DBF Breaker Failure Protection |