Table 5F Ð Superheat Charging Table, 50SS048 (Carrier Scroll Compressor)

TEMP (F)

 

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

 

1600

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

65

 

SPH

15.5

15.5

15.6

15.6

17.6

 

19.6

 

21.6

 

22.8

24.0

25.2

25.2

25.3

70

 

SPH

11.7

11.8

11.8

11.8

13.9

 

16.0

 

18.0

 

20.1

22.2

24.3

24.3

24.3

75

 

SPH

8.0

8.0

8.0

8.0

10.2

 

12.3

 

14.5

 

17.4

20.4

23.3

23.3

23.3

80

 

SPH

6.0

6.0

6.0

6.0

8.7

 

11.3

 

13.9

 

16.3

18.6

20.9

21.5

22.0

85

 

SPH

*

*

*

*

7.2

 

10.3

 

13.4

 

15.1

16.8

18.5

19.7

20.8

90

 

SPH

*

*

*

*

5.6

 

7.7

 

9.9

 

12.4

15.0

17.6

18.7

19.8

95

 

SPH

*

*

*

*

*

 

5.2

 

6.3

 

9.8

13.2

16.7

17.7

18.8

100

 

SPH

*

*

*

*

*

 

*

 

5.8

 

9.1

12.5

15.8

17.1

18.4

105

 

SPH

*

*

*

*

*

 

*

 

5.2

 

8.4

11.7

14.9

16.5

18.1

110

 

SPH

*

*

*

*

*

 

*

 

6.2

 

8.8

11.4

14.0

15.9

17.8

115

 

SPH

*

*

*

*

*

 

*

 

7.1

 

9.1

11.1

13.1

15.3

17.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

*Do not attempt to charge system under these conditions Ð refrigerant slugging may occur.

Ewb Ð Entering Wet Bulb

 

SPH Ð Superheat at Compressor (F)

 

Table 5G Ð Superheat Charging Table, 50SS048 (Copeland Scroll Compressor)

TEMP (F)

 

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

 

1600

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

 

64

 

66

 

68

70

72

74

76

65

 

SPH

19.0

19.0

19.0

19.0

21.7

 

24.3

 

26.0

 

27.7

27.9

28.2

28.4

28.6

70

 

SPH

15.4

15.4

15.4

15.4

18.1

 

20.8

 

22.5

 

24.1

25.1

26.1

27.1

28.1

75

 

SPH

11.9

11.9

11.9

11.9

14.6

 

17.2

 

18.9

 

20.6

22.3

24.0

25.8

27.5

80

 

SPH

8.4

8.4

8.4

8.4

11.0

 

13.7

 

15.4

 

17.0

19.5

22.0

24.5

27.0

85

 

SPH

5.0

5.0

5.0

5.0

7.5

 

10.1

 

11.8

 

13.5

16.7

20.0

23.2

26.4

90

 

SPH

*

*

*

*

*

 

6.6

 

9.0

 

11.4

14.7

17.9

21.1

24.4

95

 

SPH

*

*

*

*

*

 

*

 

6.2

 

9.4

12.6

15.9

19.1

22.3

100

 

SPH

*

*

*

*

*

 

*

 

*

 

7.3

10.6

13.8

17.0

20.3

105

 

SPH

*

*

*

*

*

 

*

 

*

 

5.3

8.5

11.8

15.0

18.2

110

 

SPH

*

*

*

*

*

 

*

 

*

 

*

6.9

11.2

15.5

19.8

115

 

SPH

*

*

*

*

*

 

*

 

*

 

*

5.3

10.6

16.0

21.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

*Do not attempt to charge system under these conditions Ð refrigerant slugging may occur.

Ewb Ð Entering Wet Bulb

 

SPH Ð Superheat at Compressor (F)

 

Table 5H Ð Superheat Charging Table, 50SS060 (Carrier Scroll Compressor)

TEMP (F)

 

 

 

 

 

EVAP AIR Ð CFM

 

 

 

 

 

 

 

 

 

 

 

1600

 

 

 

 

 

 

AIR ENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

 

 

 

COND

 

 

 

 

 

 

 

 

 

 

 

 

 

54

56

58

60

62

64

66

 

68

70

72

74

76

65

 

SPH

8.9

8.9

9.0

9.0

12.1

15.2

18.3

 

20.4

22.4

24.5

24.5

24.5

70

 

SPH

5.0

5.0

5.0

5.0

7.4

11.1

14.7

 

17.3

19.9

22.5

22.9

23.3

75

 

SPH

*

*

*

*

*

6.9

11.2

 

14.3

17.3

20.4

21.3

22.1

80

 

SPH

*

*

*

*

*

*

5.6

 

9.4

13.1

16.8

18.4

19.9

85

 

SPH

*

*

*

*

*

*

*

 

*

8.9

13.3

15.4

17.6

90

 

SPH

*

*

*

*

*

*

*

 

*

6.4

11.3

13.3

15.3

95

 

SPH

*

*

*

*

*

*

*

 

*

*

9.2

11.1

13.1

100

 

SPH

*

*

*

*

*

*

*

 

*

*

7.2

9.7

12.3

105

 

SPH

*

*

*

*

*

*

*

 

*

*

5.1

8.3

11.5

110

 

SPH

*

*

*

*

*

*

*

 

*

*

*

6.9

10.8

115

 

SPH

*

*

*

*

*

*

*

 

*

*

*

5.5

10.0

LEGEND

*Do not attempt to charge system under these conditions Ð refrigerant slugging may occur.

Ewb Ð Entering Wet Bulb

 

SPH Ð Superheat at Compressor (F)

 

30

Page 30
Image 30
Carrier 50SX024-060, 50SS018-060 owner manual 1600