Carrier 50SS018-060, 50SX024-060 owner manual Dimensions Units 50SS048,060 With Optional Base Rail

Models: 50SS018-060 50SX024-060

1 48
Download 48 pages 10.79 Kb
Page 5
Image 5

REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL Ð in. (mm)

Unit Top

. 14 (356)

Duct Side of Unit

. . 2 (51)

Side Opposite Ducts

. 14 (356)

Bottom of Unit

. . . . . 0

Vertical Discharge First 12 in. (305) of Supply Duct

. . 1 (25)

NECESSARY REQUIRED CLEARANCES Ð in. (mm)

 

 

Between Units, Control Box Side

42 (1067)

Unit and Ungrounded Surfaces, Control Box Side

. 36 (914)

Unit and Block or Concrete Walls and Other Grounded

 

Surfaces, Control Box Side

42 (1067)

REQUIRED CLEARANCES FOR SERVICING Ð in. (mm)

Evaporator Coil Access Side . . . . . . . . . . . . . . . . . . . . . . . 30 (762) Control Box Access Side . . . . . . . . . . . . . . . . . . . . . . . . . 30 (762)

(Except for Necessary Requirements)

Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914) Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 (762)

UNIT

 

 

 

CENTER OF GRAVITY (in./mm)

50SS

 

 

X

 

 

Y

 

Z

048

 

 

21.7/550

 

19.7/501

 

15.7/400

060

 

 

22.0/560

 

19.9/506

 

15.7/399

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

CG

Ð

Center of Gravity

 

NEC

Ð

National Electrical Code

COND

Ð

Condenser

 

REQ'D

Ð

Required

MAT'L

Ð

Material

 

 

 

 

 

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor-fan dis- charge.

2. Dimensions in ( ) are in millimeters.

UNIT

ELECTRICAL

UNIT WT

 

CORNER WT (Lb/Kg)

 

50SS

CHARACTERISTICS

Lb

Kg

A

B

C

 

D

 

 

 

 

 

 

 

 

 

048

208/230-1-60, 208/230-3-60, 460-3-60

352

160

87/40

73/33

136/62

 

56/25

060

208/230-1-60, 208/230-3-60, 460-3-60

379

172

70/32

104/47

125/57

 

80/36

Fig. 5 Ð Dimensions; Units 50SS048,060 With Optional Base Rail

5

Page 5
Image 5
Carrier 50SS018-060, 50SX024-060 owner manual Dimensions Units 50SS048,060 With Optional Base Rail