TROUBLESHOOTING COOLING CHART (cont)

SYMPTOM

CAUSE

REMEDY

Integrated control motor

Blower wheel not secured to shaft.

Properly tighten blower wheel to shaft.

(units 50SX048 208/230 v

 

 

Insufficient voltage at motor

Determine cause and correct.

and 50SX060)

 

 

IFM does not run.

Power connectors not properly seated

Connectors should snap easily; do not force.

Integrated control motor (units

Motor programmed with a delay pro®le

Allow a few minutes for motor to shut off.

50SX048 208/230 v

 

 

With thermostat in OFF the voltage on

If measured voltage is more than 1¤2, the ther-

and 50SX060)

G,Y1,Y/Y2,W with respect to common,

mostat is incompatible with motor. If voltage is

IFM runs when it should be off.

should be less than 1¤2 of actual low

less than 1¤2, the motor has failed.

 

voltage supply

 

Integrated control motor (units

Water dripping into motor

Verify proper drip loops in connector wires.

50SX048 208/230 v

 

 

Connectors not ®rmly seated

Gently pull wires individually to be sure they

and 50SX060)

 

are crimped into the housing.

IFM operation is intermittent.

 

 

 

IFM Ð Indoor (Evaporator) Fan Motor

 

 

43

Page 43
Image 43
Carrier 50SS018-060, 50SX024-060 owner manual Troubleshooting Cooling Chart