TROUBLESHOOTING COOLING CHART

SYMPTOM

CAUSE

REMEDY

Compressor and con-

Power failure

Call power company.

denser fan will not

 

 

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker.

start.

Defective thermostat, contactor, transformer,

Replace component.

 

 

or control relay

 

 

Insufficient line voltage

Determine cause and correct.

 

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

 

Thermostat setting too high

Lower thermostat setting below room temperature.

 

Single-phase units with scroll compressor

DO NOT bypass this compressor time delay Ð wait

 

(50SS048,060 and 50SX) have a 5-minute time delay

for 5 minutes until time-delay relay is deenergized.

Compressor will not

Faulty wiring or loose connections in

Check wiring and repair or replace.

start but condenser

compressor circuit

 

fan runs.

Compressor motor burned out, seized, or

Determine cause. Replace compressor.

 

 

internal overload open

 

 

Defective run/start capacitor, overload,

Determine cause and replace.

 

or start relay

 

 

One leg of 3-phase power dead

Replace fuse or reset circuit breaker.

 

 

Determine cause.

Three-phase scroll

Scroll compressor is rotating in the

Correct the direction of rotation by reversing the

compressor

wrong direction

3-phase power leads to the unit.

(50SS048, 060;

 

 

50SX036-060

 

 

units only) makes ex-

 

 

cessive noise, and

 

 

there may be a low

 

 

pressure differential.

 

 

Compressor cycles

Refrigerant overcharge or undercharge

Reclaim refrigerant, evacuate system, and recharge

(other than normally

 

to capacities shown on nameplate.

satisfying thermostat).

 

 

Defective compressor

Replace and determine cause.

 

 

Insufficient line voltage

Determine cause and correct.

 

Blocked condenser

Determine cause and correct.

 

Defective run/start capacitor, overload

Determine cause and replace.

 

or start relay

 

 

Defective thermostat

Replace thermostat.

 

Faulty condenser-fan motor or capacitor

Replace.

 

Restriction in refrigerant system

Locate restriction and remove.

Compressor operates

Dirty air ®lter

Replace ®lter.

continuously.

Unit undersized for load

Decrease load or increase unit size.

 

 

Thermostat set too low

Reset thermostat.

 

Low refrigerant charge

Locate leak, repair and recharge.

 

Leaking valves in compressor

Replace compressor.

 

Air in system

Reclaim refrigerant, evacuate system and recharge.

 

Condenser coil dirty or restricted

Clean coil or remove restriction.

Excessive head

Dirty air ®lter

Replace ®lter.

pressure.

 

 

Dirty condenser coil

Clean coil.

 

 

Refrigerant overcharged

Reclaim excess refrigerant.

 

Air in system

Reclaim refrigerant, evacuate system and recharge.

 

Condenser air restricted or air short-cycling

Determine cause and correct.

Head pressure too low.

Low refrigerant charge

Check for leaks, repair and recharge.

 

Compressor valves leaking

Replace compressor.

 

Restriction in liquid tube

Remove restriction.

Excessive suction

High heat load

Check for source and eliminate.

pressure.

 

 

Compressor valves leaking

Replace compressor.

 

 

Refrigerant overcharged

Reclaim excess refrigerant.

Suction pressure too

Dirty air ®lter

Replace ®lter.

low.

 

 

Low refrigerant charge

Check for leaks, repair and recharge.

 

 

Metering device or low side restricted

Remove source of restriction.

 

Insufficient evaporator air¯ow

Increase air quantity. Check ®lter Ð replace if

 

 

necessary.

 

Temperature too low in conditioned area

Reset thermostat.

 

Outdoor ambient below 40 F

Install low-ambient kit.

 

Field-installed ®lter-drier restricted

Replace.

 

 

 

42

Page 42