BLOWER

SHELF

FILLER

BRACKET

RACEWAY

PLUG ASSEMBLIES

Fig. 24 Ð Filler Bracket and Blower Shelf

HORIZONTAL DUCT OPENING

Fig. 25 Ð Housing Placed for Vertical Air¯ow

ACCESSORY DUCT FLANGE KIT INSTALLATION Ð Refer to Fig. 26 for duct adapter dimensions and hole locations.

1.Mark hole locations shown in Fig. 26.

2.At marked locations, drill holes using a no. 26 (.147-in.) twist drill.

3.Partially secure duct ¯anges using two of the no. 10, 1¤2-in. screws provided.

4.See the following caution. Using remaining holes in duct ¯anges as templates, drill the remaining holes with the no. 26 (.147-in.) drill.

Do not drill deeper than 1¤2-in. into shaded area shown in Fig. 26. Damage to refrigerant coil could result.

5.Fully secure the duct ¯anges using the remaining screws provided.

The ®nished kit installation accommodates a 143¤4-in. x

143¤4-in. duct.

NOTE: Do not drill more than 1¤2-in. deep in shaded area.

Fig. 26 Ð Duct Flange Kit Ð Locating Holes

(Typical)

Step 6 Ð Provide for Condensate Disposal

NOTE: Be sure that condensate-water disposal methods com- ply with local codes, restrictions, and practices.

Unit disposes of condensate through a 3¤4-in. NPT ®tting which exits through the compressor access panel. See Fig. 2-9 for location of condensate connection.

Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground-level installations. Install a ®eld-supplied conden- sate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to pre- vent the pan from over¯owing. See Fig. 27. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.

If the installation requires draining the condensate water away from the unit, install a 2-in. trap using a 3¤4-in. FPT connection. See Fig. 27. Make sure that the outlet of the trap is at least 1 in. lower than the unit drain-pan condensate con- nection to prevent the pan from over¯owing. Prime the trap with water. Connect a drain tube using a minimum of 3¤4-in. PVC, 3¤4-in. CPVC, or 3¤4-in. copper pipe (all ®eld supplied). Do not undersize the tube. Pitch the drain tube downward at a slope of at least 1 in. for every 10 ft of horizontal run. Be sure to check the drain tube for leaks. Prime trap at the be- ginning of the cooling season start-up.