REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL Ð in. (mm)

 

Unit Top

. . 14 (356)

Duct Side of Unit

. . . . 2 (51)

Side Opposite Ducts

. . 14 (356)

Bottom of Unit

. . . . . . 0

Vertical Discharge First 12 in. (305) of Supply Duct

. . . . 1 (25)

NECESSARY REQUIRED CLEARANCES Ð in. (mm)

 

 

Between Units, Control Box Side

. . 42 (1067)

Unit and Ungrounded Surfaces, Control Box Side

. . 36 (914)

Unit and Block or Concrete Walls and Other Grounded

 

Surfaces, Control Box Side

. . 42 (1067)

REQUIRED CLEARANCES FOR SERVICING Ð in. (mm)

 

 

Evaporator Coil Access Side

. . 30 (762)

Control Box Access Side

. . 30 (762)

(Except for Necessary Requirements)

 

Unit Top

. . 36 (914)

Side Opposite Ducts

. . 30 (762)

UNIT

 

 

 

CENTER OF GRAVITY (in./mm)

50SS

 

 

X

 

 

Y

 

Z

048

 

 

21.9/555

 

19.6/498

 

13.4/341

060

 

 

22.2/565

 

19.8/503

 

13.4/340

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

CG

Ð

Center of Gravity

 

NEC

Ð

National Electrical Code

COND

Ð

Condenser

 

REQ'D

Ð

Required

MAT'L

Ð

Material

 

 

 

 

 

NOTES:

1.

Clearances must be maintained to prevent recirculation of air from outdoor-fan dis-

 

charge.

2.

Dimensions in ( ) are in millimeters.

UNIT

ELECTRICAL

 

UNIT WT

 

CORNER WT (Lb/Kg)

 

50SS

CHARACTERISTICS

Lb

 

Kg

A

B

C

D

 

 

 

 

 

 

 

 

 

048

208/230-1-60, 208/230-3-60, 460-3-60

332

 

151

82/37

68/31

131/60

51/23

060

208/230-1-60, 208/230-3-60, 460-3-60

359

 

163

65/30

99/45

120/55

75/34

Fig. 4 Ð Dimensions; Units 50SS048,060 Without Base Rail