REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL Ð in. (mm)

Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356) Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (51) Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . 14 (356) Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 Vertical Discharge First 12 in. (305) of Supply Duct . . . . . . . 1 (25)

NECESSARY REQUIRED CLEARANCES Ð in. (mm)

Between Units, Control Box Side . . . . . . . . . . . . . . . . 42 (1067) Unit and Ungrounded Surfaces, Control Box Side . . . . . . 36 (914) Unit and Block or Concrete Walls and Other Grounded

Surfaces, Control Box Side . . . . . . . . . . . . . . . . . . . 42 (1067)

REQUIRED CLEARANCES FOR SERVICING Ð in. (mm)

 

Evaporator Coil Access Side

Control Box Access Side

. 30 (762)

(Except for Necessary Requirements)

 

Unit Top

. 36 (914)

Side Opposite Ducts

. 30 (762)

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge.

2. Dimensions in (

) are in millimeters.

 

 

 

 

 

 

 

 

UNIT

 

CENTER OF GRAVITY (in./mm)

 

50SX

 

X

Y

Z

 

024

 

21.5/546

20.8/528

15.0/380

030

 

21.7/550

20.7/527

15.0/380

 

036

 

20.6/524

20.1/510

15.0/380

 

 

 

LEGEND

 

 

CG

Ð Center of Gravity

NEC

Ð

National Electrical Code

COND

Ð

Condenser

REQ'D

Ð

Required

MAT'L

Ð

Material

 

 

 

UNIT

ELECTRICAL

 

UNIT WT

 

CORNER WT (Lb/Kg)

 

50SX

CHARACTERISTICS

Lb

 

Kg

A

B

C

D

024

208/230-1-60

290

 

132

72/33

67/30

104/47

47/21

030

208/230-1-60

293

 

133

71/32

69/31

105/48

48/22

036

208/230-1-60, 208/230-3-60, 460-3-60

311

 

142

85/39

59/27

117/53

50/23

Fig. 7 Ð Dimensions; Units 50SX024-036 With Optional Base Rail

7

Page 7
Image 7
Carrier 50SS018-060, 50SX024-060 owner manual Dimensions Units 50SX024-036 With Optional Base Rail