LEGEND

 

CG

Ð Center of Gravity

NEC Ð National Electrical Code

COND Ð

Condenser

REQ'D Ð Required

MAT'L

Ð

Material

 

REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL Ð in. (mm)

Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)

Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)

Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0

Vertical Discharge First 12 in. (305) of Supply Duct . . . . . . . . . . . 1 (25)

NECESSARY REQUIRED CLEARANCES Ð in. (mm)

 

Between Units, Control Box Side

. . .

. . . . 42 (1067)

Unit and Ungrounded Surfaces, Control Box Side

. . . . . 36 (914)

Unit and Block or Concrete Walls and Other Grounded

 

Surfaces, Control Box Side

. . . . 42 (1067)

REQUIRED CLEARANCES FOR SERVICING Ð in. (mm)

 

Evaporator Coil Access Side

. . . . . 30 (762)

Control Box Access Side

. . . . . 30 (762)

(Except for Necessary Requirements)

 

Unit Top

. . . . . 36 (914)

Side Opposite Ducts

. . . . . 30 (762)

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.

2. Dimensions in ( ) are in millimeters.

 

 

UNIT

CENTER OF GRAVITY (in./mm)

 

 

 

 

 

 

50SX

X

 

 

Y

 

 

 

Z

 

 

 

 

 

 

042

20.8/529

 

20.2/512

 

17.3/440

 

 

 

 

 

048

21.6/548

 

19.8/502

 

17.3/440

 

 

 

 

 

 

060

22.0/560

 

19.9/506

 

15.7/399

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

ELECTRICAL

UNIT WT

 

 

CORNER WT (Lb/Kg)

 

50SX

 

CHARACTERISTICS

Lb

 

Kg

 

A

 

B

 

C

 

D

042

208/230-1-60, 208/230-3-60, 460-3-60

329

 

150

89/40

 

64/29

124/56

 

52/24

048

208/230-1-60, 208/230-3-60, 460-3-60

360

 

164

89/40

 

75/34

138/63

 

58/26

060

208/230-1-60, 208/230-3-60

 

379

 

172

70/32

 

104/47

125/57

 

80/36

Fig. 9 Ð Dimensions; Units 50SX042-060 With Optional Base Rail (cont)

11

Page 11
Image 11
Carrier 50SS018-060, 50SX024-060 owner manual Corner WT Lb/Kg 50SX