| LEGEND |
|
CG | Ð Center of Gravity | NEC Ð National Electrical Code | |
COND Ð | Condenser | REQ'D Ð Required | |
MAT'L | Ð | Material |
|
REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL Ð in. (mm)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Vertical Discharge First 12 in. (305) of Supply Duct . . . . . . . . . . . 1 (25)
NECESSARY REQUIRED CLEARANCES Ð in. (mm) |
| |
Between Units, Control Box Side | . . . | . . . . 42 (1067) |
Unit and Ungrounded Surfaces, Control Box Side | . . . . . 36 (914) | |
Unit and Block or Concrete Walls and Other Grounded |
| |
Surfaces, Control Box Side | . . . . 42 (1067) | |
REQUIRED CLEARANCES FOR SERVICING Ð in. (mm) |
| |
Evaporator Coil Access Side | . . . . . 30 (762) | |
Control Box Access Side | . . . . . 30 (762) | |
(Except for Necessary Requirements) |
| |
Unit Top | . . . . . 36 (914) | |
Side Opposite Ducts | . . . . . 30 (762) |
NOTES:
1.Clearances must be maintained to prevent recirculation of air from outdoor- fan discharge.
2. Dimensions in ( ) are in millimeters.
|
| UNIT | CENTER OF GRAVITY (in./mm) |
|
|
|
| ||||||||
|
| 50SX | X |
|
| Y |
|
|
| Z |
|
|
|
| |
|
| 042 | 20.8/529 |
| 20.2/512 |
| 17.3/440 |
|
|
|
| ||||
| 048 | 21.6/548 |
| 19.8/502 |
| 17.3/440 |
|
|
|
| |||||
|
| 060 | 22.0/560 |
| 19.9/506 |
| 15.7/399 |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
UNIT |
| ELECTRICAL | UNIT WT |
|
| CORNER WT (Lb/Kg) |
| ||||||||
50SX |
| CHARACTERISTICS | Lb |
| Kg |
| A |
| B |
| C |
| D | ||
042 | 329 |
| 150 | 89/40 |
| 64/29 | 124/56 |
| 52/24 | ||||||
048 | 360 |
| 164 | 89/40 |
| 75/34 | 138/63 |
| 58/26 | ||||||
060 |
| 379 |
| 172 | 70/32 |
| 104/47 | 125/57 |
| 80/36 |
Fig. 9 Ð Dimensions; Units 50SX042-060 With Optional Base Rail (cont)
11