2. OPERATION LOGIC

2.2. MONITORING AND RECORDING FUNCTIONS

2.2.1 MEASUREMENT

The DBF system provides the continuous measurement of phase and ground current values.

These measurements can be accessed directly on the liquid crystal display (HMI) on the front of the relay, or via the GE-LOCALcommunication software.

2.2.2 ASSOCIATED BREAKER STATUS

The DBF system monitors the associated breaker status through the digital inputs 52/b (or 52/a), and it is displayed on the local HMI or through the communications software.

2.2.3 TARGET LAMPS

The DBF incorporates 17 LED target lamps, one fixed LED (two colors) assigned to the system ready function, and 16 user configurable red LEDs. These configurable LEDs are arranged in two columns of 8 LEDs each. The configuration is done using the GE-INTRO software, and it consists on assigning an internal event (or an AND gate of internal events) to an LED. The LED can be configured to have memory (if Vdc is removed or the event causing the operation of the LED gets deactivated) or not and to blink or to be steady. The internal events must be previously defined using the internal signals of the relay. It is possible to use AND, OR and NOT logic gates to define these events. The available internal signals are listed in the following table.

The TARGET RESET button allows testing all target lamps if it is pushed for a short time (lighting up all of them), or resets the sealed-in targets if it remains pressed for three seconds or more.

Please refer to GE_INTRO (configuration software) Instruction book (GEK-105594) for further information.

INTERNAL PROTECTION STATUS SIGNALS

Group

Status

Comment

1.0

Program Initiate

Relay starts running (Vdc just applied).

1.1

Settings change

User changes any setting

1.2

Write Counters

User sets a value for any counter

1.3

Configuration Change

User changes relay configuration

1.4

External Trigger

Oscillography triggered by Dig. Input

1.5

Communications Trigger

Osc. triggered by HMI or GE_LOCAL

1.6

Reset Operation

Latched Relays Reset received

1.7

 

 

1.8

 

 

1.9

 

 

1.10

 

 

1.11

 

 

1.12

 

 

1.13

 

 

1.14

 

 

1.15

 

 

2.0

Input Nº 1

Digital Input #1 Status

2.1

Input Nº 2

Digital Input #2 Status

2.2

Input Nº 3

Digital Input #3 Status

2.3

Input Nº 4

Digital Input #4 Status

2.4

Input Nº 5

Digital Input #5 Status

2.5

Input Nº 6

Digital Input #6 Status

2.6

 

 

GEK-106168E

DBF Breaker Failure Protection

5

Page 12
Image 12
GE GEK 106168E manual Monitoring and Recording Functions, Measurement, Associated Breaker Status, Target Lamps