4. TECHNICAL CHARACTERISTICS
COMMUNICATIONS
- Mode: Half duplex
Typical power output : | |
Receiver sensitivity | |
Numeric aperture N.A. | 0.5 |
Wave length | 660 nm (visible red) |
| |
Typical power output: | |
Receiver sensitivity | |
Numeric aperture N.A. | 0.2 |
Wave length | 820 nm (near infrared) |
SMA type connector |
|
STANDARDS
The DBF system complies with the following standards, which include the GE insulation and electromagnetic compatibility standard and the standards required by Community Directive 89/336 for the EC market, in line with European standards. It also complies with the European directive requirements for low voltage, and the environmental and operating requirements established in ANSI standards C37.90, IEC
Test | Standard | Class |
Insulation test voltage | IEC | 600V, 2kV |
| 50/60 Hz 1 min. |
|
Impulse voltage | IEC | 5kV,0.5 J |
1 MHz interference | IEC | III |
Electrostatic discharge | IEC | IV |
| EN | 8kV |
Immunity to radio interference | IEC | III |
•Electromagnetic fields radiated with | ENV 50140 | 10 V/m |
amplitude modulation |
|
|
•Electromagnetic fields radiated with | ENV 50141 | 10 V/m |
amplitude modulation. Common mode |
|
|
•Electromagnetic fields radiated with | ENV 50204 | 10 V/m |
frequency modulation |
|
|
•Fast transients | IEC | IV |
| EN |
|
•Magnetic fields at industrial | EN | 30 Av/m |
frequency |
|
|
•RF emission | EN 55011 | B |
DBF Breaker Failure Protection | 23 |