6. ACCEPTANCE TESTS

8.Check that after 3P NO I TIMER T3 (2s), the following contacts are closed:

A12-B12 C1-D1

C4-D4 C6-D6

C5-D5 C7-D7

9.If the relay is provided with an expansion board, check that also the following contacts are closed:

E1-F1 E2-F2

E3-F3 E4-F4

E5-F5 E6-F6