2. OPERATION LOGIC
OR5 to the bottom input of AND4. Any pair of single BF initiation signals placed at AND5, AND6, or AND7 will activate the top input of AND4. This input to AND4 can also be ON if there is a 3P BF Initiation and Severe Fault 3P setting is set to ‘permitted’.
Ground Overcurrent Breaker Failure Unit.
The breaker failure action based in this ground overcurrent function basically performs an additional breaker failure function through AND19, when the 3P BF Initiate (or 2 Single Pole BF Initiate, if Low Load 2P setting is set to ‘permitted’) is present atOR10 and a ground current higher than Neutral Pickup setting is detected.
Breaker Failure without current (or very low current).
DBF includes internal logic to cover also
Breaker Arc Detection Device.
This function may close one output of the relay when it detects that: the circuit breaker is open and some amount
of current is present in any phase. There are two settings available for this function: ‘Internal Arc Pickup’ to set the current threshold and ‘Internal Arc Timer’ to coordinate the operation time of the unit with the time it takes for the breaker and auxiliary elements to open.
If the circuit breaker is open, then the 52/b contacts will energize the digital inputs corresponding to the circuit breaker status (terminals
Reset of Latching Relays
The DBF breaker failure protection may be ordered with an expansion board, which includes two latching relays that are operated in different ways depending on the number of steps selected (for additional reference see Figure 1), and will fix the tripping output once the breaker failure function has operated. A digital input through
4 | DBF Breaker Failure Protection |