GE GEK 106168E Oscillography Mask, Functions Permitted, Independent for each table, 50BF Settings

Models: GEK 106168E

1 65
Download 65 pages 63.31 Kb
Page 25
Image 25
Oscillography Mask

3. SETTINGS

Common to all tables

Range

Default

Step

 

Oscillography Mask

 

 

Prefault Cycles

2-10

4

1

Arc Detection

Enable-Disable

Enable

 

Pickup

Enable-Disable

Enable

 

1st Stage trip

Enable-Disable

Enable

 

2nd Stage Trip

Enable-Disable

Enable

 

50BF A Trip

Enable-Disable

Enable

 

50BF B Trip

Enable-Disable

Enable

 

50BF C Trip

Enable-Disable

Enable

 

50BF 3P Trip

Enable-Disable

Enable

 

External Trigger

Enable-Disable

Enable

 

Communications Trigger

Enable-Disable

Enable

 

Hi-Set A Pickup

Enable-Disable

Enable

 

Hi-Set B Pickup

Enable-Disable

Enable

 

Hi-Set C Pickup

Enable-Disable

Enable

 

50BF A Init.

Enable-Disable

Enable

 

50BF B Init.

Enable-Disable

Enable

 

50BF C Init.

Enable-Disable

Enable

 

Lo-Set A Pickup

Enable-Disable

Enable

 

Lo-Set B Pickup

Enable-Disable

Enable

 

Lo-Set C Pickup

Enable-Disable

Enable

 

3P 50BF Init.

Enable-Disable

Enable

 

Neutral Pickup

Enable-Disable

Enable

 

Arc A Pickup

Enable-Disable

Enable

 

Arc B Pickup

Enable-Disable

Enable

 

Arc C Pickup

Enable-Disable

Enable

 

Functions Permitted

50BF 1P function

Permitted-Non-Permitted

Non-Permitted

 

50 BF 3P Function

Permitted-Non-Permitted

Non-Permitted

 

3P No I Function

Permitted-Non-Permitted

Non-Permitted

 

 

 

 

 

Independent for each table

Range

Default

Step

 

50BF Settings

 

 

PH Hi-Set Pickup

1-12A

2A

0.01A

PH Lo-Set Pickup

1-12A

1A

0.01A

Neutral Pickup

0.50-6A

1A

0.01A

1 Phase Timer T1

0.05-2s

0.5s

0.01s

3 Phase Timer T2

0.05-2s

1s

0.01s

3P No I Timer T3

0.05-2s

2s

0.01s

BF Logic (3P/2P)

2-Phases/3 Phases

2-Phases

 

Severe Fault 3P

Permitted-Non-Permitted

Non-Permitted

 

Low Load 2P

Permitted-Non-Permitted

Non-Permitted

 

Output Stages number

1-2

1

1

2nd Stage Timer

0.05-2s

2s

0.01s

 

 

 

 

 

Internal Arc Settings

 

 

Internal Arc Pickup

0.05-1A

1A

0.01A

Internal Arc Timer

0.10-2s

1s

0.01s

18

DBF Breaker Failure Protection

GEK-106168E

Page 25
Image 25
GE GEK 106168E Oscillography Mask, Functions Permitted, Independent for each table, 50BF Settings, Internal Arc Settings