SETTING OUT

8. KEYBOARD AND DISPLAY

If the setting entered is outside the limits of the valid range, the relay will not accept the change and will show the following message:

SETTING OUT

OF RANGE

Some settings do not accepts numeric values; instead of that, different possibilities will be shown by pressing left/right arrow keys.

To perform MODIFY OF PROTECTION COUNTERS, the available menus are:

Level 1

Level 2

Level 3

Valid Range

MODIFY COUNTERS PROTECTION

 

I2t A COUNTER

0-999999

 

I2t B COUNTER

0-999999

 

I2t C COUNTER

0-999999

 

Nº A OPENINGS

0-9999999

 

Nº B OPENINGS

0-9999999

 

Nº C OPENINGS

0-9999999

 

 

GEK-106168E

DBF Breaker Failure Protection

45

Page 52
Image 52