2. OPERATION LOGIC

Group

Status

Comment

2.7

 

Optional Exp. Board

2.8

Input Nº 7

Digital Input #7 Status

2.9

Input Nº 8

Digital Input #8 Status

2.10

Input Nº 9

Digital Input #9 Status

2.11

Input Nº 10

Digital Input #10 Status

2.12

Input Nº 11

Digital Input #11 Status

2.13

Input Nº 12

Digital Input #12 Status

2.14

Input Nº 13

Digital Input #13 Status

2.15

Input Nº 14

Digital Input #14 Status

3.0

Breaker Failure Logic

BF Logic = 3P

3.1

Hi-Set A Pickup

Output of Hi-Set current detector ph A

3.2

Hi-Set B Pickup

Output of Hi-Set current detector ph B

3.3

Hi-Set C Pickup

Output of Hi-Set current detector ph C

3.4

50BF Pole A Initiate

CC1 Dig. Input ON (default configuration)

3.5

50BF Pole B Initiate

CC2 Dig. Input ON (default configuration)

3.6

50BF Pole C Initiate

CC3 Dig. Input ON (default configuration)

3.7

Lo-Set A Pickup

Output of Lo-Set current detector ph A

3.8

Lo-Set B Pickup

Output of Lo-Set current detector ph B

3-9

Lo-Set C Pickup

Output of Lo-Set current detector ph C

3.10

50BF 3 Phase Initiate

CC7 Dig. Input ON (default configuration)

3.11

50BF Neutral Initiate

Output of Neutral current detector

3.12

Internal Arc A Pickup

Output of AND 16 in figure 1

3.13

Internal Arc B Pickup

Output of AND 17 in figure 1

3.14

Internal Arc C Pickup

Output of AND 18 in figure 1

3.15

 

 

4.0

Pickup

Any BF signal is activated. Output of OR

7 in figure 1

 

 

4.1

Trip 1

Any unit (except Internal Arc) has tripped.

Output of OR 6 in figure 1

 

 

 

 

Same as Trip 1 when 1 step is selected.

4.2

Trip 2

2nd stage when 2 steps are selected.

 

 

Output of AND 14 / 15 in figure 1

4.3

Internal Arc

Trip from Internal Arc unit. Output of

Timer 4 in figure 1

 

 

4.4

 

 

4.5

 

 

4.6

 

 

4.7

 

 

4.8

 

 

4.9

 

 

4.10

 

 

4.11

 

 

4.12

 

 

4.13

 

 

4.14

 

 

4.15

 

 

5.0

Phase A Trip

Output of Timer 1 phase A in figure 1

5.1

Phase B Trip

Output of Timer 1 phase B in figure 1

5.2

Phase C Trip

Output of Timer 1 phase C in figure 1

5.3

Three-Pole Trip with Current

Output of Timer 2 in figure 1

5.4

Three-Pole Trip without Current

Output of Timer 3 in figure 1

5.5

Second Stage Trip

Output of AND 14 / 15 in figure 1

5.6

 

 

5.7

 

 

5.8

 

 

6

DBF Breaker Failure Protection

GEK-106168E

Page 13
Image 13
GE GEK 106168E manual Group Status Comment Optional Exp. Board