REPLACING THE BATTERY
To replace the battery:
1.Turn off all connected loads, then turn off the UPS (batteries are NOT
2. | Use a Phillips head screwdriver to remove the two top cover screws from | Steps 2 and 3 |
| the back of the UPS. |
|
3. | Slide the top panel backward 1/2" (13mm). Slide the front panel upward, |
|
| then pull outward to remove it. |
|
4. | Gently pull the batteries out of the UPS. |
|
5. | Remove the black wire from the negative |
|
| the positive (+) terminal. |
|
6. | Verify that the replacement battery matches the dimensions and battery | Steps 4 and 5 |
| type in the Specifications section below. | |
|
|
7.Connect the battery leads to the new batteries. Be sure to reconnect the red wire to the positive (+) terminal and the black wire to the negative
terminal. | - |
Note: Small sparks may occur at the battery connectors during | |
reconnection. |
|
8.Slide the batteries into the UPS.
9.Reposition the front panel and slide downward until it slides into place. Slide the top panel forward until flush with the front panel. Reinsert the two top cover screws removed in Step 2.
Dispose of the old batteries properly at an appropriate recycling facility.
TROUBLESHOOTING
If the UPS malfunctions during operation, check the following chart for proper adjustment. For further assistance, please contact your local Emerson Network Power representative.
Problem | Possible Causes | Solutions | |
|
|
| |
| The UPS may not be turned on. | • Press the On/Off button to turn on the UPS. | |
Utility power is normal, but LED 1 is not illuminated. | The power cord may not be connected properly. | • Connect the power cord securely into a wall outlet. | |
| The upstream input circuit breaker may be tripped. | • Reset the input circuit breaker. | |
|
|
| |
LED 2 flashes (amber) every 3 seconds, but there is | Battery voltage may be too low. | • Recharge the UPS for 8 hours. | |
no output power. | |||
|
| ||
|
|
| |
Alarm buzzer beeps continuously although utility | The UPS may be overloaded (check LED 2). | • Disconnect some equipment from the UPS. | |
power is normal. | |||
|
| ||
|
|
| |
UPS does not provide expected backup time. | The UPS battery reached end of life. | • Replace the internal battery. | |
|
|
| |
The UPS is on and connected to input power, but fails | Utility power may be outside the unit’s operating range. | • If utility power is normal, try reconnecting input | |
to operate properly. | power and restarting the UPS. | ||
| |||
|
|
|
SPECIFICATIONS
Model Number |
| ||
|
|
|
|
Capacity (VA/W) | 1000/600 |
| 1500/900 |
|
|
|
|
Net Weight, lb. (kg) | 23.8 (10.8) |
| 27.8 (12.6) |
|
|
|
|
Shipping Weight, lb. (kg) | 26.0 (11.8) |
| 30.0 (13.6) |
|
|
| |
Dimensions - W x D x H, in. (mm) | 5.8 x 14.2 x 9.2 (147 x 360 x 234) | ||
|
|
| |
| |||
|
| ||
50/60Hz ±5Hz | |||
|
| ||
Output Voltage (Mains Normal) | Typical | ||
|
| ||
Output Voltage (Battery Operation) | 120VAC ±5% | ||
|
| ||
Stepped sinewave | |||
|
|
|
|
Battery Type - VDC x Ah x Quantity | 12V x 7Ah x 2 |
| 12V x 9Ah x 2 |
|
|
| |
Typical Recharge Time | |||
|
|
| |
Battery Run Time* - Full Load |
| 6 minutes | |
|
| ||
Battery Run Time* - Half Load | |||
|
| ||
Audible and Visual | Audible alarm / LED | ||
|
| ||
Backup Outlets | NEMA | ||
|
| ||
Surge Outlets | NEMA | ||
|
| ||
Operating Temperature, °F (°C) | 32 to 104 (0 to 40) | ||
|
| ||
Storage Temperature, °F (°C) | 5 to 104 | ||
|
| ||
Operating / Storage Relative Humidity | |||
|
| ||
EMI Classification | FCC Part 15 Class B | ||
|
|
|
|
Agency |
|
|
|
|
|
| |
Safety | UL 1778, | ||
|
| ||
Transportation | ISTA Procedure 1A Certification | ||
|
|
|
|
* Battery run time may vary depending on load |
|
|
|
© 2008 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners.
Technical Support / Service | United States |
1050 Dearborn Drive | |
upstech@emersonnetworkpower.com | P.O. Box 29186 |
Web site: www.liebert.com | Columbus, OH 43229 |