TROUBLESHOOTING (continued)

 

 

TROUBLESHOOTING (continued)

Series 185

 

 

 

 

 

 

 

 

Problem

 

Cause and Solution

 

 

 

 

The ATS does not immediately

1.

Verify that the Generator Acceptable light is on. If it is off, see previous trouble-

transfer the load to the

 

shooting problem. The ATS will not transfer the load to an unacceptable source.

generator.

2.

Wait approximately 10 seconds for the transfer to generator time delay. This

 

 

 

fixed delay allows the generator output to stabilize before a load is applied to it.

 

3.

Press the Bypass Time Delay button for immediate load transfer to the generator.

 

 

 

The ATS transfers the load to

1.

The generator may be overloaded. Check to see if the generator circuit breaker

the generator, but the genera-

 

tripped. Check the sum of the loads to be sure it does not exceed the capacity of

tor bogs down (struggles or

 

the generator. Some motor loads require three times more power for starting.

slows down). The ATS retran-

2.

Check for short circuit in a connected load.

 

sfers back to the utility.

 

 

3.

Observe the Load on Utility and Load on Generator lights.

 

 

 

The generator stops after a

1. Verify proper generator operation; it may have run out of fuel or shut down

running for awhile. The ATS

 

because of low oil level (see generator manual).

 

retransfers back to the utility

2.

The generator may be overloaded. Check to see if the generator circuit breaker

(if acceptable).

 

tripped. Check the sum of the loads to be sure it does not exceed the capacity of

 

 

 

 

the generator. Some motor loads require three times more power for starting.

 

3.

Check for short circuit in a connected load.

 

 

4.

Observe the Load on Utility and Load on Generator lights.

 

 

 

 

The ATS does not retransfer

1.

Verify that the Utility Acceptable light is on. The ATS will not transfer the load to

the load back to the utility.

 

an unacceptable source.

 

 

2.

Wait approximately 5 minutes for the retransfer to utility time delay. The utility

 

 

must be acceptable for 5 minutes continuously.

 

 

3.

Press the Bypass Time Delay button for immediate load retransfer to the utility.

 

 

 

The ATS retransfers the load

1.

Wait approximately 2 minutes for the unloaded running (engine cooldown) time

back to the utility but the

 

delay.

 

generator keeps running.

2.

The engine cooldown fixed time delay is important to prevent generator damage.

 

 

 

 

 

The generator exerciser does

1.

Verify that the Automatic Generator Exerciser status light is blinking.

 

not seem to work.

 

--- Light blinks during the exercise period.

 

 

 

(when the generator is running and during cooldown).

 

 

 

--- Light stays on when then exerciser has been set.

 

 

 

--- When light is off, no exercise period is set.

 

 

2.

With ALL POWER OFF, verify that the exerciser is turned on. Check DIP switch

 

 

S1 actuator 7, and S2 actuator 10. See Table B for generator exerciser settings.

 

3.

With ALL POWER OFF, check the 9 volt battery. Replace, if necessary, with a

 

 

quality alkaline battery: Duracell MN1404, Everready 522, Panasonic 6AM6, or

 

 

equivalent. See Figure 5.

 

 

 

 

The generator exerciser does

1.

With ALL POWER OFF, verify that exercise with load is turned on. Check DIP

not transfer the load to the

 

switch S1 actuator 8. See Table B for generator exerciser settings.

 

generator.

 

 

 

9

381333–319 E