CONTROLLER

Series 185

CONTROLLER

 

 

The Group 4 digital Controller is used in ASCO Series 185 automatic transfer switches. It provides the sensing, timing, and control functions for the ATS. This micro– processor–based controller includes built–in control buttons and status lights for control of the ATS and generator.

clock battery cover see page 3

 

 

Utility

 

 

Acceptable

 

 

light

Transfer

 

Load on

Test

 

 

Utility light

 

button

 

 

 

Bypass

 

 

Time Delay

 

 

 

 

button

 

 

Set Engine

 

 

Exerciser

 

Load on

button

 

Generator

 

 

light

Automatic

 

Generator

Generator

 

Acceptable

Exerciser

 

light

light

 

 

Figure 3. Front view of controller.

1 --- Push Buttons

On the front control display are three push buttons that control the operation of the generator and the ATS.

Before using the transfer test button, be sure that conditions are safe for running the generator and for load transfer.

Transfer Test

Use this button to test the system. This operation starts the generator and transfers the load. Be sure that conditions are safe to do this operation.

Bypass Time Delay

Use this button to cancel the active time delay or exercise period (stops the generator after cooldown).

Set Engine Exerciser

Use this button to set the automatic generator exerciser (page 3).

2 --- Indicator Lights

On the front control display are five lights that indicate the status of the sources and the ATS.

Utility Acceptable

This light indicates that the utility voltage is acceptable for connection to the load.

Generator Acceptable

This light indicates that the generator voltage is acceptable for connection to the load.

Load on Utility

This light indicates that the load is connected to the utility.

Load on Generator

This light indicates that the load is connected to the generator.

Automatic Generator Exerciser

This light indicates the status of the generator exerciser:

---blinks during the exercise period (including cooldown).

---stays on when the exerciser has been set.