| CONTROLLER (continued) | Series 185 | |
|
|
|
|
6 Remote Control & Load | 7 | Summary |
These remote control features require a customer– supplied
Remote test
Table E. Remote test
Function | Factory | DIP | DIP | Actuator | |
Setting | Switch | Actuator | Position | ||
| |||||
disabled | disabled | S3 | 3 | on (up) | |
enabled | (on) | off (down) | |||
|
|
Remote test (with automatic retransfer)
Table F. Remote transfer to generator
Function | Factory | DIP | DIP | Actuator | |
Setting | Switch | Actuator | Position | ||
| |||||
disabled | disabled | S3 | 2 | on (up) | |
enabled | (on) | off (down) | |||
|
|
Bypass load transfer to utility time delay
Table G. Bypass load transfer to utility delay
Function | Factory | DIP | DIP | Actuator | |
Setting | Switch | Actuator | Position | ||
| |||||
disabled | disabled | S3 | 1 | on (up) | |
enabled | (on) | off (down) | |||
|
|
Load disconnect feature
Connect external circuits to the terminals indicated on the wiring diagram. The double throw (Form C) contact operates prior to a selectable 0, 3, 10, or 20 second delay before transfer of the ATS. The contact resets either immediately following transfer or after the same delay as set for presignal before transfer. Time delay between the load disconnect control signal and initiation of transfer is set on the controller DIP switch S3 (actuators 6, 7, 8).
*Enabling the delay after transfer will cause the control signal to reset after the same delay as set for the delay before transfer.
Table H. Factory Settings – Summary
DIP Switch | DIP Actuator | Actuator Position | |
|
|
| |
| 1 | on (up) | |
|
|
| |
| 2 | off (down) | |
|
|
| |
| 3 | on (up) | |
|
|
| |
| 4 | off (down) | |
|
|
| |
S1 | 5 | off (down) | |
|
| ||
6 | on (up) | ||
| |||
|
|
| |
| 7 | off (down) | |
|
|
| |
| 8 | off (down) | |
|
|
| |
| 9 | off (down) | |
|
|
| |
| 10 | on (up) | |
|
|
| |
| 1 | off (down) | |
|
|
| |
| 2 | on (up) | |
|
|
| |
| 3 | off (down) | |
|
|
| |
| 4 | on (up) | |
|
|
| |
S2 | 5 | on (up) | |
|
| ||
6 | on (up) | ||
| |||
|
|
| |
| 7 | on (up) | |
|
|
| |
| 8 | on (up) | |
|
|
| |
| 9 | off (down) | |
|
|
| |
| 10 | off (down) | |
|
|
| |
| 1 | on (up) | |
|
|
| |
| 2 | on (up) | |
|
|
| |
| 3 | on (up) | |
|
|
| |
| 4 | on (up) | |
|
|
| |
S3 | 5 | on (up) | |
|
| ||
6 | off (down) | ||
| |||
|
|
| |
| 7 | on (up) | |
|
|
| |
| 8 | on (up) | |
|
|
| |
| 9 | on (up) | |
|
|
| |
| 10 | on (up) | |
|
|
|
Table I. Load disconnect delay before transfer
Function | Factory | DIP | DIP | Actuator | |
Setting | Switch | Actuator | Position | ||
| |||||
0 seconds | disabled | S3 | 7 | on (up) | |
8 | on (up) | ||||
|
|
| |||
3 seconds |
| S3 | 7 | on (up) | |
| 8 | off (down) | |||
|
|
| |||
10 seconds |
| S3 | 7 | off (down) | |
| 8 | on (up) | |||
|
|
| |||
20 seconds |
| S3 | 7 | off (down) | |
| 8 | off (down) | |||
|
|
|
Table J. Load disconnect delay after transfer*
Function | Factory | DIP | DIP | Actuator | |
Setting | Switch | Actuator | Position | ||
| |||||
disabled | disabled | S3 | 6 | off (down) | |
enabled |
| S3 | 6 | on (up) |
5 |