Liebert iCOM® Control
Liebert® CRV84
Figure 74 Set alarms parameters screen - Page 2
Customer Input 1, 2, 3 & 4—These parameters select the device and operation of the customer
inputs. Each event reflects a different alarm and possible action to the unit. Refer to table 7 for a
description of selectable options.
Customer Input 1, 2, 3 & 4 active when—These parameters select whether the input is a normally
closed or normally closed input.
Figure 75 Set alarms parameters screen - Page 3
This screen selects the operation of an active alarm. Each event can be enabled or disabled and can be
set to operate as an alarm, warning or message. The delay is the time the control waits before
reporting the event.
• Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display
• Warning / Alarm: Annunciates the buzzer, triggers a monitoring event, shows the event in the
event viewer / front display and flashes the red LED on the display.
• Message: Shows the event in the event viewer and on the front display.
S211
S212
S213
S214
S215
S216
S217
S218
S219
S220
S221
PASSWOR D (Actual Level 0) ????
Customer In put 1 Smoke Alarm
Customer In put 1 activ e when Closed
Customer In put 2 Fire Alarm
Customer In put 2 activ e when Closed
Customer Input 3 C PMP Alarm SD
Customer In put 3 activ e when Closed
Customer In put 4 HUM
Customer In put 4 activ e when Closed
SET ALARMS (page 2 of 4) UNIT 01
to change parameter
for next/previous unit to select parameter
to confirm
then
S223
S224
S225
S226
S227
S228
S229
S230
S231
S232
S233
PASSWOR D (Actual Level 0) ????
DELAY EN-DIS TYPE
LOSS OF POWER ENABLE WRN
SMOKE DETECTED 5 ENABLE ALM
WATER UNDER FLOOR 5 ENABLE ALM
LOSS OF FLOW 5 ENABLE ALM
CUSTOMER INPUT 1 5 ENABLE ALM
REHEAT LOCKOUT 5 ENABLE ALM
HUMIDIFIER LOCKOUT 5 ENABLE ALM
COMPRESSOR(S) LOCKOUT 5 ENABLE ALM