Figure 85 Rack Overview, Page 1This screen shows the rack label assigned to each rack and the temperature associated with the rack sensor. This screen shows the relative distance between the Liebert CRV and each rack sensor.Figure 86 Rack Setup, Page 1Rack Sensors are automatically detected when connected and set to “Control.” A maximum of 10 2T sensors can be connected; the control automatically detects the type.Control—The Liebert CRV is using the sensor for temperature control.Reference—The sensor value is shown, but not used for temperature control.Disable—No sensor connected.
Rack Overview (page 1 of 1) UNIT 01
All temperatures shown in °F
Cold Aisle
1
77
CC21
2
78
BB01
3
78
BB02
4
77
BB03
78
EC50
5
EC51
6
to change parameter
for next/previous unit to select parameter
to confirm
then
S901
S902
S903
S904
S905
S906
S907
S908
S909
S910
S911
PASSWORD Actual Level 0) ????
Remote Sens or Node 01 Control
Remote Sens or Node 02 Control
Remote Sens or Node 03 Control
Remote Sens or Node 04 Control
Remote Sens or Node 05 Control
Remote Sens or Node 06 Control
Remote Sens or Node 07 Disable
Remote Sens or Node 08 Disable
Remote Sens or Node 09 Disable
Remote Sens or Node 10 Disable
RACK SETUP (page 1 of 3) UNIT 01