Single Stage Connections
Refer to equipment manufacturers' instructions for specific system wiring information..
This thermostat is designed to operate a
You can configure the thermostat for use with the following systems:
WIRING CONNECTIONS
Single stage gas, oil or electric..
HEAT PUMP TYPE 1 (HP 1). Single stage compressor system; gas or electric backup..
After wiring, see INSTALLER CONFIGURATION section for proper thermostat configuration.
Single Stage System with Single Transformer
Jumper
To Remote Temperature Sensor
{
| B | O | Y | G | RC RH C* | + | S | - | W | 6 |
| L | ||||||||||||||||
System |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| Blower/ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Circula- |
|
|
|
|
|
| DC |
|
| DC |
|
|
|
|
|
|
| ||||
Single |
|
|
|
| Energized | tor Fan |
|
|
|
| 24 Volt | supply | Remote | Return |
| Third | Diagnostic | |||||||||||
Stage | Energized | Energiz- | on call | Energiz- | 24 Volt | 24 Volt | Com- | voltage | Temp- | to | Energized | |||||||||||||||||
wire for | Indicator | |||||||||||||||||||||||||||
(SS) | in Heat | ed in | for Cool | ed on | (Hot) | (Hot) | mon | to re- | erature | Remote | on call for | |||||||||||||||||
| or Off | Cool | (Com- | call for | mote | (See | ||||||||||||||||||||||
| Cool | Heat | (option- | Sensor | Temp- | Heat | zone | Note 1 ) | ||||||||||||||||||||
| Mode | Mode | pressor) | Cool & |
|
|
|
| al) | Temp- | signal | erature |
| valve |
|
|
|
| ||||||||||
|
|
|
|
|
|
| for Heat |
|
|
|
|
|
| erature |
|
| Sensor |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| (if ELE |
|
|
|
|
|
| Sensor |
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| is sel- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ected) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NEUTRAL
24VAC | 120VAC |
HOT
*Common connection required for fault or
malfunction indication and remote sensor..CLASS II
TRANSFORMER
Single Stage with Two Transformers
|
|
|
|
|
|
|
|
|
|
| Remove Jumper Wire |
|
|
|
| To Remote Temperature Sensor |
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
| between RH & RC |
| Jumper |
|
|
|
|
| { |
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| B | O | Y | G RC RH C* | + |
| S | - | W | 6 | L | |||||||||||||||||
|
|
|
|
| System |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Blower/ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| Energized | Circula- |
|
|
|
|
|
|
| DC |
|
|
| DC |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| tor Fan |
|
|
|
|
| 24 Volt | supply |
| Remote | Return |
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| on call | Energiz- |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
| Single | Energized | Energized | 24 Volt | 24 Volt |
| Com- | voltage |
| Temp- | to | Energized | Third wire | Diagnostic | ||||||||||||||||
|
|
|
|
| Stage | in Heat, | in Cool | for Cool | ed on | (Hot) | (Hot) |
| mon | to re- |
| erature | Remote | on call for | for | Indicator | ||||||||||||||
|
|
|
|
| (Com- | call for |
|
| ||||||||||||||||||||||||||
|
|
|
|
| (SS) | Off Mode | Mode | Cool | Heat |
| (option- | mote |
| Sensor | Temp- | Heat | zone valve | (See | ||||||||||||||||
|
|
|
|
| pressor) | Heat or |
|
| ||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| al) | Temp- |
| signal | erature |
|
|
|
| Note 1 ) | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| Cool |
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| erature |
|
|
| Sensor |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| (if ELE |
|
|
|
|
|
|
| Sensor |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| is sel- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| ected) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NEUTRAL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
120VAC |
|
|
|
| 24VAC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| HOT |
|
|
|
|
|
|
|
|
|
|
|
| *Common connection required for fault or | |||||||||||||||
HEATING |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
| CLASS II |
|
|
|
|
|
|
|
|
|
|
|
|
| malfunction indication and remote sensor.. |
TRANSFORMER
NOTE: If continuous backlight or hardwired power input are desired but do not function in both HEAT and COOL modes, cut the heating transformer 24V wires and tape off.. Connect the neutral circuit disconnected from the heating transformer to the neutral circuit of the cooling transformer.. Discon- nect the wire to the RH terminal and install a jumper between RH and RC.. Depending on the system requirements, replace the cooling transformer with a 75VA class II transformer if needed..
NEUTRAL
24VAC | 120VAC |
HOT
COOLING
CLASS II
TRANSFORMER
Heat Pump Systems
To Remote Temperature Sensor
|
|
|
|
|
|
|
|
|
|
| Jumper |
|
|
|
| { |
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| B | O | Y | G RC RH C* | + |
| S | - | W | 6 |
| L |
|
|
|
| ||||||||||||||||||
System |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| 1st | Blower/ |
|
|
|
|
|
| DC |
|
|
| DC | Auxil- | Power |
|
|
|
|
|
|
|
| ||||||
| Energiz- |
|
|
| Circula- |
|
|
|
|
|
| supply |
| Remote | Closed |
|
|
|
|
|
|
|
| |||||||||||
|
|
|
| Stage |
|
|
|
|
|
|
| Return | iary & |
|
|
|
|
|
|
|
| |||||||||||||
| ed in | Energized | tor Fan |
|
|
|
|
|
| voltage |
| Conn- | Diagnostic |
|
|
|
| |||||||||||||||||
Heat | Heat/ | in Cool | Heat | Energiz- | 24 VAC | 24 VAC | 24 VAC | to re- |
| Temp- | to | Emer- | ection | Indicator |
|
|
|
| ||||||||||||||||
Pump 1 | Emer- | & Off | & Cool | ed on | (Hot) | (Hot) | Common | mote |
| erature | Remote | gency | for | (See |
|
|
|
| ||||||||||||||||
(HP1) | gency | Mode | (Com- | call for | Cool | Heat | (optional) | Temp- |
| Sensor | Temp- | Heat | Note ) | Comfort |
|
| ||||||||||||||||||
| Mode |
|
|
| pressor) | Heat or |
|
|
|
|
|
| erature |
| signal | erature | 1st | zone |
|
|
|
| Alert II module |
|
| |||||||||
|
|
|
|
|
| ** | Cool |
|
|
|
|
|
| Sensor |
|
|
| Sensor | Stage | valve |
|
|
|
| or similar |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| malfunction |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| module |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| NEUTRAL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 24VAC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HOT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*24 VAC common connection optional for system operation..
Required for fault or malfunction indi- cation, remote temperature sensor, or for continuous backlight operation..
**Dual fuel
compressor when auxiliary heat is
energized..
120VAC
CLASS II
TRANSFORMER
NOTE ➀: Connection for Call for Service diagnostic indicator compatible with mechanical or electronic condenser control with Comfort AlertTM..3