Emerson 1F97-1277 specifications Installer/Configuration Menu

Models: 1F97-1277

1 12
Download 12 pages 56.04 Kb
Page 5
Image 5
INSTALLER/CONFIGURATION MENU

INSTALLER/CONFIGURATION MENU

To enter the menu: Press the Menu touch key.. Press and hold for 5 seconds the Installer Config touch key.. This displays menu item #1 in the table below.. Press CONFIGURATION MENU to advance to the next menu item or Manual background to return to a previous menu item.. Press Manual background or Manual background to change a menu item..

Installer Note: To default the programming, clock and Configuration Menu to the Factory Default Settings, press the Manual background, Manual background and SYSTEM keys simultaneously.. The thermostat display will go blank for a few seconds, and then all segments will display momentarily.. For heat pump systems, Configuration Menu item 1 must be set to match the heat pump system.

If first item does not show SS1 or HP1, you have an earlier thermostat model and need Instruction Sheet 37-6814D.

CONFIGURATION MENU

Menu

 

Non-

 

Displayed

Press

or

 

 

to

 

 

 

 

 

Reference

Program-

Program-

Press

(Factory

select from listed

 

Number

mable

mable

Button

Default)

options

 

Comments

1

1

1

 

SS1

HP1, SS1

 

Selects Single Stage or Heat Pump

 

 

 

 

 

 

 

 

 

 

(1 compressor)

2

2

2

 

(ELE)

 

GAS

 

GAS setting: furnace controls blower

 

 

 

 

 

 

 

 

 

 

ELE setting: thermostat controls blower

3

3

3

 

Days, (7) P

5+1+1 or 0

 

Programs per week.. (0 = non-programmable)

 

 

 

 

 

 

 

 

 

 

 

4

4

NA

 

PS (4)

 

2

 

 

 

Program periods per day

 

 

 

 

 

 

 

 

 

 

4 = Morning, Day, Evening, Night

 

 

 

 

 

 

 

 

 

 

2 = Day, Night

5

5

4

 

Cool-Off-

Cool-Off-Heat,

 

System switch configuration in single stage

 

 

 

 

Heat-Auto

Off-Heat, Cool-Off

 

 

 

 

 

 

Cool-Off-Heat-

Cool-Off-Heat-Emer,

System switch configuration, heat pump mode

 

 

 

 

Emer-Auto

Off-Heat-Emer,

 

 

 

 

 

 

 

Cool-Off

 

 

6

6

NA

 

E (On)

 

OFF

 

Selects Energy Management Recovery, E (with programming option on)

 

 

 

 

 

 

 

 

 

 

 

7

7

5

 

Cr, Heat (FA)

 

SL

 

Selects Adjustable Anticipation, cycle rate, Heat

 

 

 

 

 

 

 

 

 

 

 

8

8

6

 

Cr, Cool (FA)

 

SL

 

Selects Adjustable Anticipation, cycle rate, Cool

 

 

 

 

 

 

 

 

 

 

 

9

9

7

 

Cr/AU, Emer (FA)

 

SL

 

Selects Adjustable Anticipation, cycle rate auxiliary, (This item is

 

 

 

 

 

 

 

 

 

 

only to appear if HP1 is selected above)

10

10

8

 

CL (OFF)

 

On

 

Selects Compressor Lockout

 

 

 

 

 

 

 

 

 

 

 

11

11

9

 

dL (On)

 

OFF

 

Selects Continuous Display backlight & intensity

 

 

 

 

 

 

 

 

 

 

 

12

12

10

 

dL (LO)

 

HI

 

Selects Backlight Intensity

 

 

 

 

 

 

 

 

 

 

13

13

11

 

0

4, LO to 4, HI

 

Selects Adjustable Ambient Temperature Display [range -4 (LO)

 

 

 

 

 

 

 

 

 

 

to +4 (HI)]

14

14

12

 

°F

 

°C

 

Selects °F/°C Display (temperature units in Fahrenheit or Celsius)..

 

 

 

 

 

 

 

 

 

 

 

15

15

13

 

b (On)

 

OFF

 

Selects audible Beeper On/Off

 

 

 

 

 

 

 

 

 

 

 

16

16

14

 

dS (On)

 

OFF

 

Selects Daylight Saving Time calculation

 

 

 

 

 

 

 

 

 

 

 

17

17

15

 

AS, Heat (On)

 

OFF

 

Selects Automatic Schedule for comfort temperature Programming,

 

 

 

 

 

 

 

 

 

 

heat mode

18

18

16

 

AS, Cool (On)

 

OFF

 

Selects Automatic Schedule for comfort temperature Programming,

 

 

 

 

 

 

 

 

 

 

cool mode

19

19

17

 

CS, (OFF)

1-2-3-4-5-6

 

 

 

Selects Cool Saving Feature & amount

 

 

 

 

Cool Savings

 

 

 

 

 

 

20

20

18

 

HL, Heat (99)

 

62-98

 

 

 

TEMPERATURE LIMIT, HEAT (max.. heat set point)

 

 

 

 

 

 

 

 

 

 

 

21

21

19

 

LL, Cool (45)

 

46-82

 

 

 

TEMPERATURE LIMIT, COOL (min.. cool set point)

 

 

 

 

 

 

 

 

 

22

22

20

 

OFF,

L (total), P (partial),

Selects Keypad Lockout

 

 

 

 

Keypad Lockout

Temperature Limit

 

 

 

 

 

 

(limited temperature

 

 

 

 

 

 

 

range)

 

 

 

 

 

 

000

001-999

 

 

 

Selects Keypad Lockout Combination (active only if keypad Lockout

 

 

 

 

 

 

 

 

 

 

is selected)..

23

23

21

 

FS, Heat (On)

 

OFF

 

Fast second stage of heat (not available if SS1 is selected above)

 

 

 

 

 

 

 

 

 

 

 

24

24

22

 

Remote (OFF)

 

On

 

Remote temperature sensor, enable/disable

 

 

 

 

 

 

 

 

 

 

 

 

 

In, Remote

Outdoor Remote

Remote temperature sensor (Indoor/Outdoor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LS (On)

 

OFF

 

Local temp.. Sensor enable/disable (only when Indoor Remote is

 

 

 

 

 

 

 

 

 

 

selected On)..

25

25

23

 

dF (5)

 

5-50

 

 

 

Selects Dual Fuel Feature & set point (in Fahrenheit)

 

 

 

 

 

 

 

 

 

 

(applicable only when HP1 is selected)

 

 

 

 

Cd (60)

 

0-99

 

 

 

Selects Compressor delay in seconds (only when dF is selected >5)

 

 

 

 

 

 

 

 

 

 

 

26

26

24

 

Change Filter

 

On

 

Selects Change filter feature

 

 

 

 

(OFF)

 

 

 

 

 

 

 

 

 

 

200 Hours

25-1975

 

 

 

Change filter, duration hours

 

 

 

 

 

(in increments

 

 

 

 

 

 

 

of 25 hours)

 

 

5

Page 5
Image 5
Emerson 1F97-1277 specifications Installer/Configuration Menu