Emerson 3350, 3700 installation instructions Use 18 to 12 AWG 0,75 to 4,0 mm2 wire

Models: 3350 3700

1 24
Download 24 pages 13.9 Kb
Page 21
Image 21

Connect the Model 3350/3700 to a power supply as follows:

1.Use 18 to 12 AWG (0,75 to 4,0 mm2) wire.

2.Using a flat-head screwdriver, loosen the captive screws that secure the display cover to the housing.

3.Ground the transmitter as follows:

Connect the ground wire to the green screw (power supply ground; see Figure 11).

Connect the power supply ground wire directly to earth ground.

Keep all ground leads as short as possible.

Ground wiring must have less than 1 ohm impedance.

4.Connect wires to terminals 9 and 10 on the gray terminal block (see Figures 11 and 12).

5.Close the display cover and tighten the screws.

6.A user-supplied switch may be installed in the power supply line. For compliance with low-voltage directive 73/23/EEC (European installations), a switch in close proximity to the Model 3350/3700 is required.

20

Page 21
Image 21
Emerson 3350, 3700 installation instructions Use 18 to 12 AWG 0,75 to 4,0 mm2 wire