Page 23
2-Position Transfer Switching 7A TS, 7N TS (Non-Bypass)
Notes: 1. Enclosures for 1600 - 4000 amp are free-standing with removable top, sides, and back.
2. Consult ASCO for dimensions on enclosures other than ULtype 1.
Depth
inches (mm)
Height
inches (mm)
Width
inches (mm)
Poles
Switch Rating
amps
7000 Series Designed to Fit Anywhere
Enclosed UL Type 12
30, 70, 100, 150, 200, 230 2, 3 or 3 with neutral A/B/C 18 (457) 48 (1219) 13 (330)
260, 400 2, 3 or 3 with neutral A/C 22 (559) 48 (1219) 13 (330)
600, 800, 1000 2, 3 or 3 with neutral A/B/C 34 (864) 72 (1829) 20 (508)
1200 2, 3 or 3 with neutral A/B/C 38 (965) 87 (2210) 23 (584)
1600, 200012, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 48 (1219)
300012, 3 or 3 with neutral A/B/C 38 (965) 91 (2311) 60 (1524)
400012, 3 or 3 with neutral A/C 46 (1168) 91 (2311) 72 (1829)
Open Configuration
30, 70, 100, 150, 200, 230 2, 3 or 3 with neutral B/C 10-1/4 (260) 10-1/4 (260) 5-1/2 (140)
260, 400 2 or 3 12 (305) 18-1/2 (470) 6-7/8 (175)
260, 400 2 or 3 with neutral C 14-1/2 (368) 18-1/2 (470) 6-7/8 (175)
600, 800, 1000, 1200 2, 3 or 3 with neutral B/C 27 (686) 31 (787) 12-7/8 (327)
1600, 2000 2, 3 or 3 with neutral B/C 33-1/4 (845) 28 (711) 26-1/4 (667)
3000 2, 3 or 3 with neutral B/C 33-1/4 (845) 28 (711) 30-3/4 (781)
4000 2, 3 or 3 with neutral C 41 (1041) 52 (1321) 25-1/2 (648)
2-Position Transfer Switching 7A TS, 7N TS
Open
lb (kg)*
Enclosed
lb (kg)
Poles
Switch Rating
amps
30, 70, 100 2 67 (31) 15 (7)
30, 70, 100 3 70 (32) 18 (8)
30, 70, 100 3 with B/C 73 (33) 21 (10)
150, 200, 230 (Open) 2 69 (32) 17 (8)
150, 200, 230 (Open) 3 72 (33) 20 (9)
150, 200, 230 (Open) 3 with B/C 75 (34) 23 (11)
230, 260, 400 2 117 (53) 37 (17)
230, 260, 400 3 125 (57) 45 (21)
230, 260, 400 3 with C 133 (61) 53 (24)
600, 800, 1000 2 400 (182) 150 (68)
600, 800, 1000 3 420 (192) 170 (78)
600, 800, 1000 3 with B/C 446 (203) 196 (90)
1200 2 685 (312) 150 (68)
1200 3 705 (321) 170 (78)
1200 3 with B/C 731 (333) 196 (90)
1600, 2000 2 1110 (503) 370 (167)
1600, 2000 3 1160 (525) 420 (190)
1600, 2000 3 with B/C 1210 (548) 470 (213)
3000 2 1365 (620) 405 (184)
3000 3 1430 (649) 470 (213)
3000 3 with B/C 1495 (679) 535 (243)
4000 2 2208 (1002) 975 (443)
4000 3 2433 (1104) 1200 (545)
4000 3 with C 2533 (1149) 1300 (590)
Shipping Weights
Notes: *Open weights include transfer switch and control panel.
1200-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.
ASCO