INSTALLATION (continued)

INSTALLATION (continued)

Tighten bolted joints to the torque specified in Table A.

The reliablility of the connection depends on how clean and how tight the joint is.

Table A. Tightening torque values for bolted joints

(Grade 5 hardware)

Bolt Diameter

Tightening Torque

in inches

in foot pounds

1/4

7

5/16

12

3/8

20

1/2

50

5/8

95

3/4

155

Controller Ground

A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.

Harnesses

The transfer switch is connected to the left side of the control panel by a plug-in harness (two plugs).

Auxiliary Circuits

Connect auxiliary circuit wires to appropriate terminals on the transfer switch. Note the control features that are furnished on this switch. Make the necessary auxiliary connections by referring to the Wiring Diagram.

Engine Starting Contacts

The engine control contact connections (if used) are located on the transfer switch. Connect signal wires to appropriate terminals as specified in Table B and shown in Figure 1---1.

Table B. Engine start connections

When normal

Terminals on

source fails

transfer switch

contact closes

TB1 and TB2

contact opens

TB1 and TB3

engine start connections on customer terminal block TB

Figure 1-1. Customer terminal block on the top right side of enclosure.

Functional Test

The Functional Test consists of three checks:

V1 — Manual Operation Test, page 1–3

V2 — Voltage Checks, page 1–4

V3 — Electrical Operation, page 1–5

Do these checks in the order presented

to avoid damaging the ATS.

Read all instructions on the Wiring Diagram and labels affixed to the ADTS. Note the control features that are provided and review their operation before proceeding.

Continue to 1 – Manual Operation Test on next page.