Emerson Series 300 manual ADJUSTMENTS continued, How to Change a Setting, Close the enclosure door

Models: Series 300

1 20
Download 20 pages 28.82 Kb
Page 14
Image 14
ADJUSTMENTS (continued)

ADJUSTMENTS (continued)

Do not make any setting changes while the controller is energized.

How to Change a Setting

1.Prevent the transfer switch from operating by discon- necting one source first, then the other, as follows:

a.If the transfer switch is in the Normal position, open the emergency source circuit breaker. Turn the engine starting control to off. Then open the normal source circuit breaker.

b.If the transfer switch is in the Emergency position, open the normal source circuit breaker. Turn engine starting control to test or run. Then open the emergency source circuit breaker.

2.Disconnect both harness plugs from controller by squeezing the latches. Do not pull on the wires.

3.Remove cover from the controller by releasing latch on right side with your thumb. See Figure 4-1.

4.Locate the appropriate adjustment potentiometer or DIP switch for the setting that you want to change. Refer to Table 4-1 and Table 4–2 on page 4-1 and Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.

5.Use a small screwdriver to turn the potentiometer clockwise to increase the time delay or counterclock- wise to decrease it. See Figure 4-3.

6.Use a ball-point pen (or similar pointed tool) to slide the switch actuators left or right so they match the il- lustration next to the setting (left = off, right = on). Recheck the setting. See Figure 4-4.

7.Install the cover on the controller by hooking it on the left side and latching the right side.

8.Reconnect both harness plugs to the controller by aligning and pressing straight in until latches click.

Close the enclosure door.

cover

thumb

 

latch

hook on left side

Figure 4-1. Controller cover latch.

 

9 volt

 

alkaline

 

battery

 

J5 battery

harness

on/off

jumper

plugs

 

 

P1

 

retransfer

 

to normal

 

time delay

S3 DIP

P2

transfer to

switch

emergency

S1 DIP

time delay

 

switch

 

 

S2 DIP

 

switch

Figure 4-2. Location of potentiometers.

clockwise to increase

P1 or P2 potentiometer

counterclockwise to decrease

Figure 4-3. Changing time delay potentiometers.

9.Close the enclosure door, then restore both sources:

a.If the transfer switch is in the Normal position first close the normal source circuit breaker, then close the emergency source circuit breaker.

b.If the transfer switch is in the Emergency position, close the normal source circuit breaker. The load will be automatically retransferred to the normal source. Then close the emergency source circuit breaker.

10. Turn the engine starting control to automatic.

4---2

DIP

switches

SW1

SW2

SW3 Do not make any setting changes while the controller is energized. actuator

(8 on each DIP switch)

off How to Change a SettingClose the enclosure door. on

Figure 4-4. Setting DIP switch actuators.

Page 14
Image 14
Emerson Series 300 manual ADJUSTMENTS continued, How to Change a Setting, Close the enclosure door