INSTALLATION (continued)
observe these lights
Figure 1–5. St andard controls and indicators.
2 – Voltage Checks
First check nameplate on transfer switch; rated voltage must be the same as normal and emergency line voltages.
Verify that the feeders have been connected to the proper lugs.
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !
Perform steps 1 through 6 at the right. Observe the status lights. See Figure
●Black circle means light is on.
❍White circle means light is off.
*If necessary, adjust voltage regulator on the generator according to the manufacturer’s recommendations. The Automatic Transfer Switch will respond only to the rated voltage specified on the Transfer Switch nameplate.
Close the normal source circuit | Source Accepted | |
breaker. The Normal Transfer | ||
1 Switch Position and the Normal | Normal | |
Source Accepted lights should | ||
Emergency | ||
come on. | ||
|
Use an accurate voltmeter to check phase to phase and
2phase to neutral voltages pres- ent at the transfer switch normal source terminals.
Close the emergency source | Source Accepted |
circuit breaker. (Start generator, | |
3 if necessary.) The Emergency | Normal |
Source Accepted light should | Emergency |
come on. |
|
Use an accurate voltmeter to check phase to phase and
4phase to neutral voltages pres- ent at the transfer switch emer- gency source terminals.*
| Use a phase rotation meter to | A B C |
|
| |
5 | check phase rotation of emer- |
|
gency source; it must be the |
| |
| same as the normal source. |
|
| Shut down the |
|
| tor, if applicable. The Emergen- | Source Accepted |
| cy Source Accepted light should | |
6 go off. Then put the starting | Normal | |
| control selector switch (on the | |
| Emergency | |
| generator set) in the automatic |
|
| position. Close enclosure door. |
|
Now continue to 3 – Electrical Operation on next page.