TESTING & SERVICE (continued)
MANUAL LOAD TRANSFER
This procedure will manually transfer the load if the controller is disconnected.
Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
1.Open normal and emergency source circuit breakers.
2.Use the maintenance handle to manually operate transfer switch to the opposite source. See page
3.If the transfer switch is in the Emergency position manually start the engine generator and then close the emergency source circuit breaker.
TROUBLE-SHOOTING
Note the control features that are activated or furnished on the switch and review their operation. Refer to Section 5, Control Features.
Proceed with care!
The automatic transfer switch is energized.
Table 3-1. Trouble-Shooting Checks.
PROBLEM | CHECK IN NUMERICAL SEQUENCE | |||
1 OPERATION | 2 | 3 VOLTAGE | ||
| ||||
Hold the Transfer Test button | Starting control must be in |
| ||
the Transfer Test button is | 15 sec. or the outage must be | automatic position. Batteries |
| |
pressed and held for 15 | long enough to allow for the 1 | must be charged and |
| |
seconds or when the normal | or 3 sec. Momentary Normal | connected. Check wiring to | — | |
source fails. | Source Outage Delay plus | engine starting contacts. |
| |
| engine cranking and starting |
|
| |
| time. |
|
| |
|
|
|
| |
Transfer switch does not | Wait for Transfer to Emergen- | Generator output circuit | Voltmeter should read at least | |
transfer the load to | cy Delay (0 to 5 min.) to time | breaker must be closed. | 90% of nominal phase to | |
emergency source after the | out. For immediate transfer, | Generator frequency must be | phase voltage between | |
press the Bypass Time Delay | at least 57 Hz. | transfer switch terminals EA | ||
| button. If Motor Load Transfer |
| and EC (or EL1 and EL2 for 2 | |
| is active, wait for inphase con- |
| pole switches). * | |
| dition (see below). |
| * These are factory settings. | |
|
|
|
| |
Transfer switch does not | Wait for Retransfer to Normal |
| Voltmeter should read at least | |
transfer the load to normal | Delay (1 sec. to 30 min.) to |
| 90% of nominal phase to | |
source when normal returns | time out. For immediate re– |
| phase voltage between | |
or when Transfer Test button | transfer, press Bypass Time | — | transfer switch terminals NB | |
is released. | Delay button. If Motor Load |
| and NC, NC and NA, and NA | |
| Transfer is active, wait for in- |
| and NB (or NL1 and NL2 for 2 | |
| phase condition (see below). |
| pole switches). | |
|
|
|
| |
Wait for the 5 minute | Starting control must be in |
| ||
load retransfer to the normal | Unloaded Running Delay to | automatic position. | — | |
source. | time out. |
|
| |
|
|
|
|
Trouble-Shooting the Motor Load Transfer Feature (refer to page 5–4)
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !
1.Connect a voltmeter (set for twice system
2.Manually start generator. Voltmeter needle should sweep back and forth at a regular rate between 0 and about twice system voltage.
3.Press and hold Transfer Test button. The load should transfer to emergency source when meter needle is near 0 volts. If transfer does not occur, Motor Load Transfer feature is not operating.
4.Release the Transfer Test button. The load should retransfer back to the normal source after the Retransfer to Normal Delay, if used. The retransfer should occur when the needle is near 0 volts. If retransfer does not occur after the time delay, the Motor Load Transfer feature is not operating.
5.For immediate retransfer, press the Bypass Time Delay button. Then disconnect the voltmeter.
If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office, representative, or ASI. In United States, call