8.WIRING CONSIDERATIONS

8.1.Power Wiring

Refer to Site Planning Data (Appendix A) and the installation drawings. Determine AC currents for your system based on kVA, kW, voltage, and options. Also refer to equipment nameplate for the model number, rating, and voltage. For wire termination data, refer to Tables 1-3.

1.Power wiring -- rectifier input, bypass input, UPS output, and battery cables -- must be run in individual, separate conduit or cable tray. Refer to the Outline and Terminal Details drawings (Figures 11-13 and 35-39) for location of the various power connections within the UPS.

CAUTION

Power and control wiring must be separated!

2.Observe local, state and national electrical codes. Verify utility power and its overcurrent protection rating will accommodate the UPS input rating, including battery recharging.

3.A safety ground wire must be run from building ground to ground point in the UPS Module Cabinet, the Battery Cabinet and the Power-Tie™ switchgear cabinet. See Sections 7.1 through 7.7. The grounding conductor shall comply with the following conditions of installation:

a.The insulated grounding conductor must be sized in accordance with the NEC and local codes. It must be green (with or without yellow stripes) and be installed as part of the branch circuit that supplies the unit or system.

b.The grounding conductor described above is to be grounded to earth at the service equip- ment or, if supplied by a separately derived system, at the supply transformer or motor- generator set in accordance with the instructions in Section 7 of this Manual.

c.The attachment-plug receptacles in the vicinity of the unit or system are all to be of a grounding type, and the grounding con- ductors serving these receptacles are to be

connected to earth ground at the service equipment.

4.Observe clockwise phase rotation of all power wiring. Phase A leads Phase B leads Phase C. A qualified electrician should check the phase rotation.

5.Power cables must be rated for less than 2 volts line drop at maximum rated system current.

6.Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 and associated notes of the National Electrical Code (NFPA 70) reprinted on page 24 of this manual.

CAUTION

The weight of power cables must be adequately supported to avoid stress on bus bars and lugs. The following restraining method is recommended to both to support cable weight and control cable movement during external fault conditions: Wrap line cables together at 6 inches and 12 inches from the terminals with 5 wraps of 3/8 inch nylon rope or equivalent (tensile strength of 2000 pounds). Support remainder of cable with 5 wraps every 6 inches or 1 wrap every 1 inch.

7.If site equipment includes a backup generator and automatic transfer switch(es), consult the manufacturers of those devices for information on sizing and interfacing to the UPS system.

8.The installing contractor can remove the access plates from the top left or top right sides of the UPS in order to cut entry holes for conduit. For units with bottom-entry cable access, there is a separate (third) access plate in the base of the unit, under the cable access wireway.

CAUTION

After cutting holes in the access plates, be certain that no foreign matter (metal shavings, sawdust, insulation or wire fragments, etc.) remains inside the UPS. Likewise be certain to block any “extra” holes in the plates through which foreign matter could later enter the UPS.

Liebert Series 600T UPS, 65-225 kVA, Single Module

15

DISCONTINUED

PRODUCT

Page 21
Image 21
Emerson SERIES 600T manual Wiring Considerations, Power Wiring

SERIES 600T specifications

The Emerson SERIES 600T, as part of the SERIES 600 line, is a sophisticated device designed to meet the demands of industrial automation and control systems. Renowned for its reliability and versatility, the SERIES 600T excels in various applications across multiple sectors, including oil and gas, chemical processing, and power generation.

One of the most significant features of the SERIES 600T is its advanced measuring capability. It offers exceptional accuracy, typically within ±0.1% of the full scale. This precision makes it suitable for critical applications where measurement integrity is paramount. The SERIES 600T is also equipped with intelligent diagnostics that can predict and monitor the health of the unit, enabling proactive maintenance and minimizing downtime. This technological advancement improves both operational efficiency and safety.

Another standout characteristic is the device's robust construction designed to withstand harsh environments. The SERIES 600T is made with durable materials that provide resistance to corrosion, vibration, and temperature extremes, making it an excellent choice for rugged industrial applications. Coupled with its IP67 rating, the device is fully sealed against dust and moisture, ensuring long-term reliability in challenging conditions.

The SERIES 600 line employs cutting-edge communication protocols, including HART and Foundation Fieldbus, facilitating seamless integration into various control systems. This capability ensures that users can easily access real-time data and manage devices remotely, significantly enhancing operational efficiency.

Additionally, the SERIES 600T supports a wide range of process connections and configurations, catering to diverse installation needs. This adaptability allows for quick deployments and minimizes the time required for system changes or upgrades.

With easy-to-read displays and user-friendly interfaces, operators can quickly interpret data and metrics from the SERIES 600T. This intuitive design helps reduce the learning curve for new users, further underlining the device's legacy of reliability and efficiency.

In essence, the Emerson SERIES 600T exemplifies cutting-edge technology in the realm of industrial measurement and automation. Its combination of accuracy, durability, diagnostic capabilities, and ease of integration makes it an ideal choice for industries that prioritize reliability and precision in their operations. As industrial processes continue to evolve, devices like the SERIES 600T will undoubtedly play a crucial role in advancing efficiency and productivity in various sectors.