3. UNLOADING AND HANDLING

3. UNLOADING AND HANDLING

Because the weight distribution in each UPS and ancillary cabinet is uneven, use extreme care during handling and transport. Your installation may also include Battery Cabinets, a Bypass Transformer Cabinet and a Maintenance Bypass Cabinet, Panelboard or Switchboard.

WARNING

EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. THE UPS MODULE CAN WEIGH UP TO TWO TONS. THE BATTERY CABINETS WEIGH UP TO 5100 POUNDS.

THE UPS MODULES ARE HEAVIER IN THE BACK THAN THE FRONT BECAUSE OF THE WEIGHT OF THE MAGNETICS. LOCATE CENTER OF GRAVITY SYMBOLS BEFORE HANDLING CABINET. TEST LIFT AND BALANCE THE CABINET BEFORE TRANSPORTING. MAINTAIN MINIMUM TILT FROM VERTICAL AT ALL TIMES.

WARNING

INTERNAL BATTERY CABINET STRAPPING MUST BE VERIFIED BY MANUFACTURER PRIOR TO MOVING THIS UNIT.

THIS UNIT CONTAINS NON-SPILLABLE BATTERIES. KEEP UNIT UPRIGHT. DO NOT STACK. DO NOT TIP.

FAILURE TO HEED THIS WARNING COULD RESULT IN SMOKE, FIRE OR ELECTRICAL HAZARD. CALL 1-800-

LIEBERT PRIOR TO RELOCATING BATTERY CABINET (AFTER INITIAL INSTALLATION).

4. INSPECTIONS

4.1. External Inspections

1.While the UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Liebert Global Services at 1-800-543-2378to inform them of the damage claim and the condition of the equipment.

2.Locate the bag containing the keys for the front access door. The bag is attached to the cabinet.

3.Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and to Liebert Global Services immediately.

4.Check the nameplate on the cabinet to verify that the model number corresponds with the one specified. Record the model number and serial number in the front of this installation manual. A record of this information is necessary should servicing become required.

4.2. Internal Inspections

1.Verify that all items have been received.

2.If spare parts were ordered, verify arrival.

3.Open doors and remove cabinet panels to check for shipping damage to internal components.

4.Check for loose connections or unsecured components in the cabinet(s).

5.Check for installation of circuit breaker line safety shields. There should be no exposed circuit breaker terminals when the cabinet doors are opened.

6.Remove any orange shipping braces or brackets from the transformers.

7.Check for any unsafe condition that may be a potential safety hazard.