Emerson SERIES 600T WIRING CONNECTIONS 9.1 Warnings, Specific Connections, Discontinued Product

Models: SERIES 600T

1 84
Download 84 pages 14.4 Kb
Page 26
Image 26
9. WIRING CONNECTIONS

9. WIRING CONNECTIONS

9.1 Warnings

DANGER

VERIFY THAT ALL INCOMING HIGH AND LOW VOLTAGE POWER CIRCUITS ARE DE-ENERGIZED AND LOCKED OUT BEFORE INSTALLING CABLES OR MAKING ELECTRICAL CONNECTIONS.

ALL POWER CONNECTIONS MUST BE COMPLETED BY A LICENSED ELECTRICIAN EXPERIENCED IN WIRING UPS EQUIPMENT, AND IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL ELECTRICAL CODES.

IMPROPER WIRING MAY CAUSE DAMAGE TO THE UPS OR INJURY TO PERSONNEL.

CAUTION

All shielded cables, non-shielded cables, non-shielded control wires, non-shielded battery breaker control wires, and non- shielded remote control wires must be housed in individual, separate, steel conduits. Placing multiple cables in the same conduit with other control or power wiring may cause system failure.

9.2 Specific Connections

Refer to the drawings in this manual and any other drawings provided by Liebert for this installation. Make all of the following connections:

a.AC power cables from input power source circuit breaker to UPS Module Input. Observe phase rotation.

CAUTION

See Section 7 of this Manual for an explanation of proper grounding techniques.

b.AC power cables from bypass power source cir- cuit breaker to UPS Module Bypass input. Observe phase rotation.

c.AC power cables from UPS Module Output to critical load. Observe phase rotation.

NOTE

If your installation includes a Maintenance Bypass Cabinet, Switchboard or Panelboard, some (or all) power cables will be terminated in these cabinet(s). Make sure all required wiring between UPS module and the optional cabinet(s) is completed. Observe phase rotation.

d.The UPS Module Output Neutral must be con- nected to one common point and solidly grounded per requirements of the National Electrical Code. See Section 7.

CAUTION

UPS bypass and output neutral must be connected to only one common point in the UPS. This neutral line must be grounded at the source.

e.For Battery Cabinets:

DC power cables and ground from Battery Cab- inet to UPS Module, and between Battery Cab- inets. Observe polarity. DC power cables should be installed in matched pairs (positive and negative).

20

Installation Manual