Emerson SERIES 600T manual Installation Considerations, Discontinued, Product

Models: SERIES 600T

1 84
Download 84 pages 14.4 Kb
Page 8
Image 8
2. INSTALLATION CONSIDERATIONS

2. INSTALLATION CONSIDERATIONS

Install your Series 600T UPS in accordance with the submittal drawing package and the following procedures.

A Liebert authorized representative must perform the initial system check-out and start- up to ensure proper system operation. Equipment warranties will be voided unless system start-up is performed by a Liebert authorized representative. Contact your local Liebert sales representative or Liebert Global Services at 1-800-543-2378to arrange for system start-up.

CAUTION

Read this manual thoroughly before attempting to wire or operate the unit. Improper installation is the most significant cause of UPS start-up problems.

Do not install this equipment near gas or electric heaters. It is preferable to install the UPS in a restricted location to prevent access by unauthorized personnel.

1.Proper planning will speed unloading, location, and connection of the UPS. Refer to Figures 11 through 58 and the Site Planning Data (Appendix A).

2.Be certain that the floor at the final equipment location and along the route (inside the facility) to the installation site can support the cabinet weight and the weight of any material handling equipment. The UPS modules can weigh up to two tons. The battery cabinets weigh between 2300 and 5000 pounds each.

3.Plan the routing to ensure that the unit can move through all aisle ways, doorways, and around corners without risking damage. If the modules and batteries must be moved by elevator, check the size of the door openings and the weight-carrying capacity of the elevator.

4.Refer to information later in this manual regarding the optional Battery Cabinet(s), Maintenance Bypass Cabinets, Panelboards and Switchboards. Observe all battery safety precautions when working on or near the battery.

5.Use the shortest output distribution cable runs possible, consistent with logical equipment arrangements and with allowances for future additions if planned.

6.Recommended ambient operating temperature is 25C (77F). Relative humidity must be less than 95%, non- condensing. Note that room ventilation is necessary, but air conditioning may not be required. Maximum ambient operating temperature for the UPS and switchgear is 40C (104F) without derating. The batteries should not exceed 25C (77F). At elevations above 4,000 feet (1219 meters) temperature derating may be required for full power output (consult your Liebert sales representative).

7.Even though your Liebert UPS unit is 92.5 to 94% efficient, the heat output is substantial. For more specific information, see the Site Planning Data (Appendix A). Be sure environmental conditioning systems can accommodate this BTU load, even during utility outages.

8.The installer should attempt to balance the load between the three output phases. The UPS will operate safely with an unbal- anced load, but will give optimum perfor- mance if the three output phases are loaded within 20 percent of each other.

DISCONTINUED

2Installation Manual

PRODUCT

Page 8
Image 8
Emerson SERIES 600T manual Installation Considerations, Discontinued, Product