Installation |
2.6Electrical Controls
2.6.1General Considerations
All shutdown devices are dry contact switches rated Class I, Division II that are wired to a terminal box for connection to the packager supplied control circuit. The common wires on all switches are connected together. All switches are closed unless a fault condition is detected.
All safety and protective devices must be installed and used in accordance with applicable codes and regulations.
Switches
All switch connections are wired to terminal strips in a junction box on the Compressor Module.
SwitchStatus
• Low Inlet Gas Pressure Normally Open, closes on pressure rise
•High Discharge Gas Pressure Normally Closed, opens on pressure rise
• High Temperature | Normally Closed, opens on temperature rise |
Electrical Considerations - Variable Speed Compressor Module
•The Compressor power for a variable speed Compressor Module is the Variable Frequency Drive (VFD).
•Compressor speed control can be either a
•Each Compressor on a module must be protected by an individual manual reset overload between the VFD and the Compressor.
•The overloads should be able to be set at a maximum of 26A.
•If either overload opens, the VFD must be disabled.
•The overloads must be configured for manual reset.
•Normal full load run current for each Compressor on the module at 4800 rpm (80 Hz) is approximately
23A.
•The customer control circuit must supply an Enable signal to the VFD before the drive will accept a Run Fwd signal.
•The VFD will start when the Enable signal is on and a Run Fwd signal is applied.
•The VFD will stop if the Run Fwd signal is off or the Enable signal is removed.
NOTE
The drive provides 24V for the Enable and Run Fwd signals.
The installer must connect the Enable and Run Forward terminals to the drive’s 24V terminal.