Dual-Compressor Module

Installation

Figure 8 Optional Customer-Installed High Temperature Fan Control System

Power Supply

24VDC

PLC

Or

Temperature

Control

SZO44

Compressor

Module

0-10VDC Fan Speed Signal

0.9V = Off; 1.3V = 50%; 10V = 100%

Temperature Sensor

Compressor requirements: 1.2 to 2 GPM (4.5-755 LPM) flow rate

Operating temperature range, standard: 190° to 210°F (88°- 99°C)

Thermal oil bypass valve, standard setting: 200°F (93°C)

Thermal bypass valve operation (valve’s purpose is to provide discharge temperature control)

Oil flow on valve is A to B when the unit is cold and A to C when the heat rises (see Figure 9).

Figure 9 Oil Cooling and Thermal Valve

1st-Stage Separator

A

C

B

Return

to Compressor

Oil Cooler

11

2006SSD-75 R4 (10/10)

Page 17
Image 17
Emerson SZV44, SZV32, SZO56 manual Temperature Control, SZO44