Specifications

Specifications

10.0SPECIFICATIONS

Table 6

Liebert XDR specifications

 

 

 

 

 

 

 

 

 

 

 

 

Models

 

XDR20B1- *

 

XDR20B1P *

 

XDR20B1R *

 

 

(Pre-Charged R-134a)

 

 

 

 

 

 

 

Cooling Capacity, Nominal,

 

 

20.5 kW (5.8 tons)

 

rated at 104ºF (40°C) EAT & 2400ft3/m (68m3/m)

 

 

 

 

 

 

 

 

Conditions

 

55°F (13°C) entering fluid temperature

 

 

50°F (10°C) or lower dew point

 

 

 

 

 

Dimensions, inches (mm)

 

 

 

 

 

 

Height, Including Pipe Connections

82-3/8 (2093)

 

83-1/2 (2121)

 

80 (2032)

 

 

 

 

 

 

 

 

Width With Handles Attached

 

27-3/8 (695)

 

 

 

 

 

 

 

 

 

Handles Removed

 

23-1/2 (597)

 

 

 

 

 

 

 

 

 

Depth

 

6-1/2 (165)

 

 

 

 

 

 

 

 

 

Shipping Length

 

90 (2286)

 

 

 

 

 

 

 

 

 

Shipping Width

 

30-1/2 (775)

 

 

 

 

 

 

 

 

 

Shipping Depth

 

15-1/2 (394)

 

 

 

 

 

 

 

 

 

Max Shipping Depth (4 modules)

 

62 (1575)

 

 

 

 

 

 

 

 

Weight, lb (kg)

 

 

 

 

 

 

Module Only

130 (59)

 

133 (60)

 

130 (59)

 

 

 

 

 

 

 

 

Shipping

225 (103)

 

228 (104)

 

225 (103)

 

 

 

 

 

 

Pipe Connections

 

 

 

 

 

 

Refrigerant Supply

 

 

1/2" OD Type ACR

 

 

 

 

 

 

 

 

Refrigerant Return

 

 

7/8" OD Type ACR

 

 

 

Exterior Finish

Black Matte, Heat-Fused Powder Coat

Safety

 

 

 

CSA, CE Approved

 

*Refer to Figure 2 for the complete part number.

Table 7

Rack mounting kit

 

 

 

Rack

 

Part #

Knurr Miracel

198163G1

Dell PowerEdge 4210

199050G1

 

 

 

HP 10642

 

199051G1

 

 

APC AR3100

199054G1

 

 

 

Table 8

Liebert XD Flex Pipe one-shot assemblies, supply and return

 

 

 

 

 

 

 

 

 

 

Length

Liebert P/N

Liebert P/N

Minimum Bend Radius

Description

Straight Connection

90-Degree

in (mm)

 

 

ft (m)

Assembly

Connection Assembly

 

 

 

 

Supply

Return

 

 

 

 

 

 

 

 

 

 

 

 

10 (3.0)

186566G2

186565G2

 

 

Liebert XD

8 (2.5)

186566G3

186565G3

7 (178)

9 (229)

Flex Pipe Kit

6 (1.8)

186566G1

186565G1

 

 

 

 

 

 

 

 

 

 

 

4 (1.2)

186566G4

186565G4

 

 

 

 

 

 

 

 

 

Table 9

Liebert XD Flex Pipe removable assemblies, supply and return

 

 

 

 

 

 

 

 

 

 

Length

Liebert P/N

Liebert P/N

Minimum Bend Radius

Description

Straight Connection

90-Degree Connection

in (mm)

 

 

ft (m)

Assembly

Assembly

 

 

 

 

Supply

Return

 

 

 

 

 

10 (3.0)

187865G2

187864G2

 

 

Liebert XD

 

8 (2.5)

187865G3

187864G3

7 (178)

9 (229)

Flex Pipe Kit

6 (1.8)

187865G1

187864G1

 

 

 

 

4 (1.2)

187865G4

187864G4

 

 