Emerson Process Management 2051 Rosemount, HART Protocol, Quick Installation Guide, FM Approvals

Models: 2051 2051CF

1 24
Download 24 pages 40.07 Kb
Page 17
Image 17
HART Protocol

Quick Installation Guide

00825-0100-4101, Rev EA June 2010

Rosemount 2051

HART Protocol

Hazardous Locations Certifications

North American Certifications
FM Approvals

E5 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II, Division 1, Groups E, F, and G. Dust-Ignition-Proof for Class III, Division 1.

T5 (Ta = 85 °C), Factory Sealed, Enclosure Type 4X

I5 Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1 when connected per Rosemount drawing 02051-1009; Non-incendive for Class I, Division 2, Groups A, B, C, and D. Temperature Code:T4 (Ta = 70 °C),

Enclosure Type 4X

For input parameters see control drawing 02051-1009.

Canadian Standards Association (CSA)

All CSA hazardous approved transmitters are certified per ANSI/ISA 12.27.01-2003.

E6 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E, F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D for indoor and outdoor hazardous locations. Class I Zone 1 Ex d IIC T5. Enclosure type 4X, factory sealed. Single Seal.

I6 Intrinsically safe approval. Intrinsically safe for Class I, Division 1, Groups A, B, C, and D when connected in accordance with Rosemount drawing 02051-1008. Temperature Code T3C. Class I Zone 1 Ex ia IIC T3C. Single Seal.

European Certifications

I1 ATEX Intrinsic Safety

Certification No. Baseefa08ATEX0129X Hazardous Locations Certifications II 1 G Ex ia IIC T4 (–60 Ta +70 °C)

IP66 IP68 North American Certifications 1180

Table 2. Input Parameters for 4-20 mA

Ui = 30V

Ii = 200 mA

Pi = 1.0W

Ci = 0.012 µF

Special Conditions for Safe Use (X):

When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding the 500V insulation test required by Clause 6.3.12 of EN60079-11. This must be taken into account when installing the apparatus.

17

Page 17
Image 17
Emerson Process Management 2051 Rosemount, HART Protocol, Quick Installation Guide, Hazardous Locations Certifications