Quick Installation Guide

Rosemount 2051

00825-0100-4101, Rev EA June 2010

Figure 7. Wiring

Trim shield and insulate

DP

Insulate Shield

Connect Shield Back to the Power Supply Ground

NOTE

Do not connect the powered signal wiring to the test terminals. Power could damage the test diode in the test connection. Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire and do not exceed 5,000 feet (1500 meters).

4.Plug and seal unused conduit connections.

5.If applicable, install wiring with a drip loop. Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing.

6.Replace the housing cover.