Installation Instructions

c. Slide the side panel out to access the high/low electrical connections and wire diagram.

8.Check wiring diagram for the required number of low voltage wires to be run between indoor and outdoor sections.

S1C

High Volt Low Volt

plastic edge guards

Note: Remove the plastic edge guards from the holes and replace with a water- tight strain relief fitting (High V) and a split grommet fitting (low V)

5.Power should be run to a weather proof disconnect box usually within 3 feet of the unit.

6.From the disconnect box, run the power through the 7/8" hole on the side of the unit and into the electrical box and an- chor with the strain relief fitting.

S1C

Shown

Low Volt Connection

9. Connect the 24 volt wiring matching color to color. Refer to the wiring diagram on the inside panel of the condenser, and

a l s orefer to the wiring diagram on the indoor unit. Low volt in- terconnect should be at least 18

awg.

S1C

Shown

High Volt Connection

7.Run wires to the high volt pigtail in the con- trol box and attach L1 and L2 connections. Also run green wire to ground wire.