Installation Instructions

REFRIGERANT PIPING

Continued

1.Clean the ends of tubing and insert into fittings.

S2C

S1C

Shown

S1C

Shown

5. Attach manifold set.

manifold

Vaccum Pump Micron Gage

2.Protect the valves by wrapping with a wet rag "heat sink" before brazing.

S1C

Shown

3.We recommend the use of a shield (can be made from some scrap metal) to protect the paint.

S1C

Shown

Manifold Setup For Evacuation

6.Evacuate line to 500 microns or less to ensure all moisture has been removed and there are no leaks.

 

S1C

 

Shown

 

Refer to Refrigerant

 

Charge Table for

 

specified line charge.

S2C

7. Once certain of a good evacuation and

Shown

 

leak free joints, back-seat the valves

 

(counter-clockwise) to open and allow

4. Braze tubing into fittings.

factory charge to fill lines and indoor unit.