EMI WLCA EMI CASSETTE - CAH/W, CAF/4, Start Up Procedures, Enviromaster International Llc

Models: WLCA

1 20
Download 20 pages 60.08 Kb
Page 6
Image 6
EMI CASSETTE - CAH/W, CAF/4

START UP PROCEDURES

8.For microprocessor controlled units, check that the display panel cable is properly connected to the microprocessor main circuit board and that the jumper links are correctly set (refer to unit wiring schematic). If the links are set incorrectly, remove main power before making any changes.

9.For microprocessor controlled units, check that the battery on the main circuit board is in place and properly connected. Check also that the bat- teries are installed in the infrared unit.

Once the above pre-start checks have been carried out sat- isfactorily, the main start up operation can begin.

IMPORTANT: The jumper links referenced in step 8 must be correctly set before applying mains power, to ensure correct operation of unit. (micro units only)

START UP SHEET EXAMPLE

 

 

 

EMI CASSETTE - CAH/W, CAF/4

 

5780 SUCCESS DRIVE

 

 

 

ENVIROMASTER INTERNATIONAL LLC

TO BE COMPLETED IN CONJUNCTION WITH START UP PROCEDURE

 

ROM E, NY 13440

RETURN ONE COPY TO EM I AND RETAIN ORIGINAL FOR YOUR RECORDS

 

TEL: 1-800-228-9364

TECHNICIAN:

COMPANY:

DATE:

FAX: 1-800-232-9364

MODEL/SERIAL NO:

PROJECT:

 

HTTP ://WWW.ENVIROM ASTER.COM

1.0 PRE START UP CHECKLIST

 

 

 

 

 

 

 

1.1 UNIT CONDITION SATISFACTORY

COMMENT:

 

 

1.2 PRESSURE TEST WITH DRY NITROGEN

INITIAL TEST

FINAL TEST

TEST DURATION

 

PRESSURE

PRESSURE

 

1.3 DESIGN WATER FLOW AVAILABLE IF

 

 

GPM

CHILLED WATER UNIT

 

 

 

1.4 VOLTAGE AT OUTDOOR UNIT

 

 

V

1.5 VOLTAGE AT INDOOR UNIT

 

 

V

1.6 ELECTRICAL CONNECTIONS TIGHT

 

 

YES/NO

1.7 JUMPERS SET CORRECTLY (MICRO ONLY)

 

 

YES/NO

2.0 START UP CHECKLIST - INDOOR UNIT

 

 

 

 

 

 

 

2.1 DISABLE COMPRESSOR SIGNAL

 

 

 

2.2 ON/OFF WORKS

 

 

YES/NO

2.3 INDOOR UNIT: THREE FANS SPEEDS

 

 

YES/NO

AVAILABLE (MICRO ONLY)

 

 

 

2.4 VANE SWEEP FUNCTIONS

 

 

YES/NO

2.5 TIMER FUNCTIONS OPERATE (MICRO ONLY)

 

 

YES/NO

2.6 CONDENSATE PUMP OPERATES

 

 

YES/NO

3.0 START UP CHECKLIST - OUTDOOR UNIT (REFER TO THE RELEVANT OUTDOOR UNIT MANUAL AND, IN ADDITION, NOTE THE FOLLOWING:

 

 

 

 

3.1 OPERATING PRESSURES

 

 

 

3.2 SUCTION

 

 

PSIG

3.3 DISCHARGE

 

 

PSIG

3.4 AMBIENT TEMPERATURE

 

 

ºF

35. INDOOR AIR TEMPERATURE

 

 

ºF

NOTE: A START UP SHEET FOR EVERY UNIT MUST BE RETURNED TO EMI TO VALIDATE THE WARRANTY.