DVVK-5F FLEX VENT INSTRUCTIONS

The DVVK-5F FLEX VENT KIT includes the following components:

 

 

• (1)

Horizontal Termination Cap

(1) Wall Firestop/Thimble Assembly

• (1)

4-foot section of Flex vent with spacers (5" flue/8" outer pipe)

Hardware pack that includes band clamps and screws

 

with flue adapter collar

 

 

Flex venting can be installed either vertically or horizontally off of the DVP Series fireplaces. When installing a horizontal vent run from top connections, maintain at least ½" rise for every 12" of vent run. When venting horizontal off the rear vent connections, allow a minimum rise of 2". Refer to the Figure 42 when mounting termination near vinyl siding.

CAUTION: Always stretch and secure venting with wire or metal strapping to ensure that the horizontal runs do not sag. If space permits, it is generally easier to attach venting in the top vent configuration.

Because of sharp edges, always use gloves when handling the flex vent components. Vent connections should overlap a minimum of 1" for proper sealing.

Always follow the general venting requirements for vent terminal location, vent lengths, and clearance to combustible materials.

INSTALLATION

1.Unpack vent components and check that all items are included.

2.Check to see that the vent spacer springs are located around the flue vent at 8" and 12" intervals along its length. See Figure A. If not, stretch the spacer springs to about 15" long and wrap them around the flue, then interlock the ends of each spring about 2". See Figure B. Maintain equal distance between spring spacers.

Figure A

SPACER

SPRINGS

FLEX OUTER VENTFLEX FLUE PIPE

8”

8”

8”

(203 mm)

(203 mm)

(203 mm)

8.Prior to making the vent connections, apply high temperature sealant (1000 degree F min.) to the vent connections before securing with the band clamps provided. Note: the flue pipe end without the adapter is to be installed to the Termination Cap.

9.Apply sealant to the outside of the flue pipe adapter and connect to the flex flue pipe. Then insert the adapter into the fireplace flue. Secure flue adapter to the fireplace flue with a minimum of two screws provided. See Figure C.

10.Attach the Outer Vent pipe to the 8" dia. Collar on the fireplace with a large band clamp provided. Sealant may also be used on the outer vent connections.

11.Check all vent connections for tightness. Make sure horizontal venting has the proper rise and combustible clearances required. Refer to venting charts in fireplace instruction manual.

8” DIA. FLEX

 

VENT PIPE

 

5” DIA. FLEX

 

FLUE PIPE

Figure C

5” DIA. FLUE

 

ADAPTOR

BAND CLAMP

COLLAR

 

8” DIA. FIREPLACE

APPLY HIGH

INLET COLLAR

TEMPERATURE

 

SEALANT

4” FLEX

SPACER

Figure B

 

 

VENT PIPE

 

 

 

SPRING

 

3.Use existing 8" dia. inlet collar to attach outer vent pipe.

4.Install the Wall Firestop/Thimble assembly as required through the wall. Refer to the venting charts in the fireplace manual to determine the proper height and size of the vent opening. The minimum opening should be 10" wide by 12" high. The minimum combustible clearance from the horizontal vent is 1" from sides and bottom, and 3" above the vent pipe. See Figure D.

5.In most cases, after determining the length of the vent that is needed, it may be easier to install the flue and outer vent pipes to the Termination Cap first, then from the outside, feed the venting through the wall to the fireplace.

6.If the venting is to long, trim off any excess vent before attaching the vent end connectors.

7.Attach the Termination Cap to the outside of the house.

17375-6-0705

Top of Vent

3"(76 mm)

Figure D

1"(25 mm)

Combustibles NOT allowed in shaded area

5” Diameter flue

8” Diameter intake vent

1" (25 mm)

Page 25

Page 25
Image 25
Empire Comfort Systems DVP48FP9, DVP48FP3, DVP42FP9, DVP48FP7, DVP42FP3, DVP42FP7 DVVK-5F Flex Vent Instructions