GAS SUPPLY

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Tubing, Type L

(Feet)

Inside Diameter

Outside Diameter

 

Nat.

LP

Nat.

LP

0-10

1/2”

3/8”

1/2”

3/8”

 

1.3cm

1.0cm

1.3cm

1.0cm

10-40

1/2”

1/2”

5/8”

1/2”

 

1.3cm

1.3cm

1.6cm

1.3cm

40-100

1/2”

1/2”

3/4”

1/2”

 

1.3cm

1.3cm

1.9cm

1.3cm

100-150

3/4”

1/2”

7/8”

3/4”

 

1.9cm

1.3cm

2.2cm

1.9cm

Note: Never use plastic pipe. Check to confirm whether your lo- cal codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code. The use of the following gas connectors is recommended:

ANS Z21.24 Appliance Connectors of Corrugated Metal Tub- ing and Fittings

ANS Z21.45 Assembled Flexible Appliance Connectors of Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flex- ible appliance connector cannot exceed three feet in length.

Figure 1

Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/ CGA-B149 (.1 or .2) installation code.

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be

checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing. It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet. This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign particles may collect.

Figure 2

Method of Installing a Tee Fitting Sediment Trap Pressure Testing of the Gas Supply System

1.To check the inlet pressure to the gas valve, a 1/8” (3mm) N.P.T. plugged tapping, accessible for test gauge connection, must be placed immediately upstream of the gas supply connection to the appliance.

2.The appliance and its individual shutoff valve must be discon- nected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa)

3.The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 (kPa).

Attention! If one of the above procedures results in pressures in excess of 1/2 psig (14” w.c.) (3.5 kPa) on the appliance gas valve, it will result in a hazardous condition.

Checking Manifold Pressure

Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 4.0” w.c. (.996kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 5.0” w.c. (1.245kPa) for the purpose of input adjustment to a maximum of 10.5” w.c. (2.61kPa). Propane gas models will have a manifold pressure approximately 10.0” w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 11.0” w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0” w.c. (3.23kPa).

A 1/8” (3mm) N.P.T. plugged tapping, accessible for test gauge connection, is located on the outlet side of the gas control.

12822-4-0806

Page 6

 

Page 6
Image 6
Empire Comfort Systems RH50C-1, RH-50-6, RH-65-6 GAS Supply, Recommended Gas Pipe Diameter, Installing a New Main Gas Cock

RH-65-6, RH-65C-1, RH-50-6, RH50C-1 specifications

Empire Comfort Systems has long been a trusted name in the heating solutions market, and their RH series of direct-vent gas heaters exemplifies their commitment to quality and innovation. Among the models in this series, the RH-50-6, RH-65-6, RH-65C-1, and RH-50C-1 stand out for their exceptional performance and user-friendly features.

The RH-50-6 offers a heat output of 50,000 BTUs, making it ideal for smaller spaces needing effective, efficient heating. It features a sleek design and a variety of style options, ensuring it can fit seamlessly into any room. Its direct vent system allows for safe and efficient operation, drawing air from the outside while expelling exhaust gases, thus creating a comfortable indoor environment without compromising indoor air quality.

Similarly, the RH-65-6 model provides a higher output of 65,000 BTUs, suitable for medium to larger areas. This model emphasizes user control with an optional remote control feature, allowing homeowners to adjust the thermostat from the comfort of their couch. The easy-to-use control panel enhances operation simplicity, catering to users of all levels of technical know-how.

The RH-65C-1 and RH-50C-1 models bring additional benefits through their contemporary styling and advanced features. Both units include Empire's exclusive Comfort Control technology. This system optimizes heat distribution throughout the room, ensuring that users experience consistent warmth without hot or cold spots. Alongside aesthetic choices, such as ceramic glass fronts and versatile trim options, these models are designed to provide both functionality and style.

One significant feature across the RH series is the emphasis on energy efficiency. These models meet stringent energy standards, helping homeowners save on utility bills while minimizing environmental impact. The advanced burner technology ensures a clean burn with minimal emissions, aligning with sustainable heating practices.

In conclusion, the Empire Comfort Systems RH-50-6, RH-65-6, RH-65C-1, and RH-50C-1 represent a blend of traditional craftsmanship and modern technology. With various BTU outputs, user-friendly controls, and striking designs, they cater to diverse heating needs, making them outstanding choices for those seeking reliable and efficient home heating solutions.