TROUBLESHOOTING

SYMPTOMS - POSSIBLE CAUSES AND CORRECTION

1.When ignitor button is pressed, there is no spark at ODS/ pilot.

a.Ignitor electrode positioned wrong - Replace pilot.

b.Ignitor electrode is broken - Replace pilot.

c.Ignitor electrode not connected to ignitor cable - Reconnect ignitor cable.

d.Ignitor cable pinched or wet. Keep ignitor cable dry - Free ignitor cable if pinched by any metal or tubing.

e.Broken ignitor cable - Replace ignitor cable.

f.Bad piezo ignitor - Replace piezo ignitor.

2.Appliance produces unwanted odors.

a.Appliance burning vapors from paint, hair spray, glues, etc. - Ventilate room. Stop using odor causing products while heater is running.

b.Gas leak - Locate and correct all leaks.

3.Appliance shuts off during use. (Pilot and main burner are off.)

a.Not enough fresh air is available for ODS/pilot to operate

-Open window and/or door for ventilation.

b.Low line pressure - Contact local gas company.

c.ODS/pilot is partially clogged - Clean ODS/pilot.

d.Defective thermocouple - Replace pilot.

4.Appliance shuts off during use. (Pilot stays on.)

a.Low line pressure - Check line pressure to the valve.

b.Defective thermopile - Check pilot flame, check wire connections, output should be a minimum of 325 millivolts across. TH/TP and TP terminals with ON/OFF/REMOTE switch off.

5.Gas odor even when control knob is in OFF position.

a.Gas leak - Locate and correct all leaks.

b.Control valve defective - Replace control valve.

6.When ignitor button is pressed, there is spark at ODS/pilot, but no ignition.

a.Gas supply turned off or manual shutoff valve closed

-Turn on gas supply or open manual shutoff valve.

b.Control knob not in PILOT position - Turn control knob to Pilot position.

c.Control knob not pressed in while in PILOT position

-Press in control knob while in PILOT position.

d.Air in gas lines when installed - Continue holding down control knob. Repeat igniting operation until air is removed.

e.ODS/pilot is clogged - Replace ODS/pilot assembly or get it serviced.

f.Gas regulator setting is not correct - Replace gas regulator.

7.ODS/pilot lights but flame goes out when control knob is released.

a.Control knob not fully pressed in - Press in control knob fully.

b.Control knob not pressed in long enough -After ODS/pilot lights, keep control knob pressed in 30 seconds.

c. Manual Shutoff valve not fully open - Fully open manual shutoff valve.

d. Thermocouple connection loose at control valve - Hand tighten until snug, then tighten 1/4 turn more.

e. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This problem could be caused by either low gas pressure or dirty or partially clogged ODS/pilot - Contact local gas company.

f.Thermocouple damaged - Replace thermocouple.

g.Control valve damaged - Replace control valve.

8.Burner does not light after ODS/pilot is lit.

a.Burner orifice clogged - Clean burner or replace main burner orifice.

b.Burner orifice diameter is too small - Replace burner orifice.

c.Inlet gas pressure is too low - Contact qualified service person.

9.If burning at main burner orifice occurs (a loud, roaring blow torch noise).

a.You must turn off burner assembly and contact a qualified service person.

b.Manifold pressure is too low - Contact local gas company.

c.Burner orifice clogged - Clean burner or replace burner orifice.

10.Logs appear to smoke after initial operation.

a.Vapors from paint or curing process of logs - Problem will stop after a few hours of operation. Run the heater with the damper open if you have one, or open a window for the first few hours.

Log heater is intended to be smokeless. Turn OFF heater and call qualified service person.

11.Heater produces a whistling noise when main burner is lit.

a.Turning control knob to HIGH position when main burner is cold - Turn control knob to LOW position and let warm up for a minute.

b.Air in gas line - Operate burner until air is removed from line. Have gas line checked by local gas company.

c.Dirty or partially clogged burner orifice - Clean burner or replace burner orifice.

12.No gas to pilot.

a.LP-regulator shut down due to inlet pressure too high - Verify LP tank regulator is installed and set at 11" to 13" w.c. Replace regulator on heater.

If the gas quality is bad, your pilot may not stay lit, the burners may produce soot and the heater may backfire when lit. If the gas quality or pressure is low, contact your local gas supplier immediately.

Page 20

25741-0-0309

Page 20
Image 20
Empire Comfort Systems VFSUR18-2 Appliance produces unwanted odors, Appliance shuts off during use. Pilot stays on

VFSUR18-2, VFSUR30-2, VFSUR24-2 specifications

Empire Comfort Systems is renowned for its innovative heating solutions, and the VFSUR series exemplifies their commitment to quality and performance. The VFSUR24-2, VFSUR30-2, and VFSUR18-2 models are direct vent, free-standing gas stoves that combine timeless design with modern technology, making them ideal for both heating and aesthetic enhancement in any living space.

One of the standout features of the VFSUR series is their impressive heating capacity. The VFSUR18-2 offers a maximum output of 18,000 BTUs, the VFSUR24-2 delivers 24,000 BTUs, and the VFSUR30-2 tops out at 30,000 BTUs. This range allows homeowners to choose a model that best fits their space and heating needs, effectively warming areas from smaller rooms to larger open living areas.

Another significant characteristic of the VFSUR models is their direct vent technology, which allows for safe and efficient ventilation. This system draws air from outside for combustion while expelling exhaust gases outside as well, creating a sealed combustion environment that enhances safety and minimizes heat loss. This technology also ensures that indoor air quality is maintained, making these stoves an excellent choice for energy-conscious homeowners.

The VFSUR series features a stylish design that incorporates a traditional look with modern elements. With various finish options and decorative doors, these stoves can complement any home décor. The large viewing window provides a cozy ambiance, allowing users to enjoy the beauty of the flames while the stove efficiently heats the space.

Additionally, the VFSUR models are equipped with an advanced millivolt system that allows for reliable operation even during power outages. This feature ensures that users will have continuous warmth regardless of external conditions. The models are also compatible with optional remote controls, providing convenience in adjusting settings from anywhere in the room.

In summary, Empire Comfort Systems VFSUR series – including the VFSUR24-2, VFSUR30-2, and VFSUR18-2 – represent a fusion of efficiency, safety, and style. With impressive BTU outputs, advanced direct vent technology, and aesthetic versatility, these gas stoves are perfect for anyone looking to enhance their home heating experience while enjoying the warmth and beauty of a traditional fireplace.