Empire Products FAW-55IP installation instructions Venting, Accessories, Description

Models: FAW-55IP

1 20
Download 20 pages 40.38 Kb
Page 18
Image 18
VENTING

VENTING

Model No. FAW-55 may be vented as shown. The vent cap must be at least 12 feet (3.7m) above the floor. Clearance to combustible construction is held by the fixed spacers at 1 inch (25mm) with B-1 vent pipe. Installation must conform to local codes.

4” (102mm) Round (all parts purchase locally except item 2)

1.Type B-1 round pipe

2.Part No. DV-648, 4” (102mm) oval-to-round flue adapter kit (see accessories)

3.Single story type B-1 gas vents require a baseplate and one pair of ceiling plate spacers.

4.Multi-story type B-1 gas vents require a baseplate, one pair of ceiling plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level.

4” (102mm) Oval (all parts purchase locally)

1.Type B-1 oval pipe

2.Single story type B-1 gas vents require a baseplate and one pair of ceiling plate spacers.

3.Multi-story type B-1 gas vents require a baseplate, one pair of ceiling plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level.

4” (102mm) Oval In-The-Wall (all parts purchase locally)

1.Type B-1 oval pipe

2.Type B-1 oval elbows

3.Single story type B-1 gas vents require a baseplate and one pair of ceiling plate spacers.

4.Multi-story type B-1 gas vents require a baseplate, one pair of ceiling plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level.

Stud space around gas vents must be free of obstructions and building paper.

 

Accessories

Part No.

Description

SOR-1

Register, side outlet, fixed register

SOK-1

Side outlet, 10” (254mm) maximum extension,

 

fixed register

ROK-1

Rear Outlet, 10” (254mm) maximum extension,

 

adjustable register

DV-651

Vent enclosure, 14” (356mm) [for room up to 96

 

1/2” (245cm) in height]

DV-665

Vent enclosure, 24” (610mm) [for rooms up to

 

106 1/2” (270.5cm) in height]

DV-666

Vent enclosure, 36” (914mm) [for rooms up to

 

118 1/2” (301cm) in height]

DV-648

4” (102mm) Oval-to-Round flue adapter kit

Use U.L. listed gas vent equipment when installing the FAW-55. For vent pipe running through walls, roof, and within one inch (25mm) of combustible construction, use B-1 (one inch (25mm) clearance to combustibles) vent pipe. Type B-2 x 4 or Type B-2 x 6 are to be used in conjunction with a Listed fire stop spacer.

Type BW gas vent pipe is available for single story or multi-story installations. Type BW gas vent pipe is to be used with the Listed base plate, ceiling plate spacers and fire stop spacers.

Accessories VENT ENCLOSURE (not shown)

Part No. ADAPTER Description

SIDEFRONT

BRACKET

Manual background BASEPLATE Manual background

SIDEFRONT

Manual background SPACER Manual background

48o ELBOWS

4” (102MM) OVAL STD.

Manual background BASEPLATE Manual background

SIDEFRONT

Page 18

12429-10-0408

Page 18
Image 18
Empire Products FAW-55IP installation instructions Venting, Accessories, Description